When using 35, 50 type indoor unit of P series, use the flare nut (for R410A) attached to the indoor unit.
Do not use the flare nut (for R407C) in the indoor unit accessory. If it is used, a gas leakage may occur or a pipe may come off.
■ Pipe size (Branch box-Indoor unit) For M or S series Indoor unit
Indoor unit type
(kW)
15
18
20
22
25
35
42
50
60
71
Pipe size (mm)
Liquid
ø
6.35
ø
6.35
ø
6.35
ø
6.35
ø
6.35
ø
6.35
ø
6.35
ø
6.35
ø
6.35
ø
9.52
Gas
ø
9.52
ø
9.52
ø
9.52
ø
9.52
ø
9.52
ø
9.52
ø
9.52
ø
12.7
ø
15.88
ø
15.88
■ Pipe size (Branch box-Indoor unit) For P series Indoor unit
Indoor unit type
(kW)
35
50
60
71
100
Pipe size (mm)
Liquid
ø
6.35
ø
6.35
ø
9.52
ø
9.52
ø
9.52
Gas
ø
12.7
ø
12.7
ø
15.88
ø
15.88
ø
15.88
■ Pipe size (Branch box-Indoor unit) For Cylinder unit and Hydrobox
Pipe size (mm)
Liquid
ø
9.52
Gas
ø
15.88
(1) Valve size of branch box for outdoor unit
For liquid
ø
9.52 mm
For gas
ø
15.88 mm
(2) Valve size of branch box for indoor unit
* UNIT
Liquid pipe
ø
6.35 mm
Gas pipe
ø
9.52 mm
* UNIT
Liquid pipe
ø
6.35 mm
Gas pipe
ø
9.52 mm
* UNIT
Liquid pipe
ø
6.35 mm
Gas pipe
ø
9.52 mm
UNIT
Liquid pipe
ø
6.35 mm
Gas pipe
ø
9.52 mm
UNIT
Liquid pipe
ø
6.35 mm
Gas pipe
ø
12.7 mm
* 3- branch type is only for
, , and unit.
Different-diameter joint (optional parts)
Type
Model name
Connected pipes
diameter
Diameter A Diameter B
mm
mm
mm
Flare
(Fig.7-1)
PAC-493PI
ø
6.35 →
ø
9.52
ø
6.35
ø
9.52
MAC-A454JP-E
ø
9.52 →
ø
12.7
ø
9.52
ø
12.7
PAC-SG76RJ-E
ø
9.52 →
ø
15.88
ø
9.52
ø
15.88
MAC-A455JP-E
ø
12.7 →
ø
9.52
ø
12.7
ø
9.52
MAC-A456JP-E
ø
12.7 →
ø
15.88
ø
12.7
ø
15.88
A
B
Fig.7-1
Conversion formula
1/4 inch
ø
6.35
mm
3/8 inch
ø
9.52
mm
1/2 inch
ø
12.7
mm
5/8 inch
ø
15.88
mm
3/4 inch
ø
19.05
mm