2-2. SYSTEM CONSTRUCTION (BRANCH BOX SYSTEM)
Outdoor unit
P112
P125
P140
4HP
5HP
6HP
Applicable indoor unit
Capacity
Type 15 to Type 100
Number of units
2 to 8 units
Total system capacity
range
*1
24 to 130 % of outdoor unit capacity
(3.0 to 16.2 kW)
21 to 130 % of outdoor unit capacity
(3.0 to 18.2 kW)
19 to 130 % of outdoor unit capacity
(3.0 to 20.2 kW)
Branch box that can
be connected
Number of units
*1
1 to 2 units
Connectable indoor unit lineup (Heat pump inverter type)
Model type
Model name
Capacity class (kW)
1.5
1.8
2.0
2.2
2.5
3.5
4.2
5.0
6.0
7.1
8.0 10.0
Wall
mounted
Deluxe
MSZ-FH25/35/50VE
●
●
●
MSZ-LN25/35/50VG(2)
●
●
●
Standard
MSZ-SF25/35/42/50VE3
●
●
●
●
MSZ-AP25/35/42/50VG(K)(D)
●
●
●
●
MSZ-GF60/71VE
●
●
MSZ-EF18/22/25/35/42/50VE(2/3)
●
●
●
●
●
●
MSZ-EF18/22/25/35/42/50VG(K)
●
●
●
●
●
●
MSZ-GE22/25/35/42/50/60/71/80VAD
●
●
●
●
●
●
●
●
Compact
MSZ-SF15/20VA
●
●
MSZ-AP15/20VF
●
●
MSZ-AP15/20VG(D)
●
●
Ceiling
concealed
Low static pressure
SEZ-KD25/35/50/60/71VAQ(L)
●
●
●
●
●
SEZ-M25/35/50/60/71DA(L)
●
●
●
●
●
Middle static
pressure
PEAD-RP50/60/71/100JA(L)Q
●
●
●
●
PEAD-RP71/100JAA(D)
●
●
PEAD-M50/60/71/100JA(L)
●
●
●
●
PEAD-M50/60/71/100JAA(D)
●
●
●
●
4-way
ceiling
cassette
2 by 2 type
SLZ-KF25/35/50VA2/3
●
●
●
SLZ-M15/25/35/50FA
●
●
●
●
Standard
PLA-RP35/50/60/71/100EA
●
●
●
●
●
PLA-M35/50/60/71/100EA
●
●
●
●
●
Ceiling suspended
PCA-RP35/50/60/71/100KAQ
●
●
●
●
●
PCA-M35/50/60/71/100KA
●
●
●
●
●
Floor standing
MFZ-KJ25/35/50VE(2)
●
●
●
MFZ-KT25/35/50VG
●
●
●
MEXZ-KW25/35/50VG
●
●
●
1-way ceiling cassette
MLZ-KA25/35/50VA
●
●
●
MLZ-KP25/35/50VF
●
●
●
N
ote: The lineup of a connectable indoor unit depends on a district/areas/country.
Connectable ecodan unit
Model type
Model name
Cylinder unit
EHST20C series (except EHST20C-MEC)
Hydrobox
EHSC series (except EHSC-MEC)
Note: Only 1 Cylinder unit or Hydrobox can be connected.
Branch box
PAC-MK54BC
PAC-MK34BC
Number of branches
(Connectable indoor unit)
5 branches
(MAX. 5 units)
3 branches
(MAX. 3 units)
Notes: 1. A maximum of 2 branch boxes can be connected to 1 outdoor unit.
2. PAC-MK31/51BC(B) cannot be used for connecting a Cylinder unit or a Hydrobox.
2- branch pipe (joint): Optional parts
In the case of using 1- branch box
No need
In the case of using 2- branch boxes
Model name
Connection method
MSDD-50AR-E
flare
MSDD-50BR-E
brazing
Select a model according to the connection method.
Option
Optional accessories of indoor units and outdoor units are available.
*1
When connecting ecodan unit(s), the total capacity of connected Air to Air indoor units is up to 130% of the outdoor unit. (Air to Air 130% + ecodan). However,
when operating Air to Air indoor unit(s) in heating mode and ecodan unit(s) in DHW or heating mode at the same time, the total capacity of connected Air to Air
units is below:
PUMY-P112: 1.3 kW, PUMY-P125: 2.8 kW, PUMY-P140: 4.3 kW
However, the following combinations can be connected:
PUMY-P112: MSZ-SF15VA or MSZ-AP15VF × 1, PUMY-P125: MSZ-SF15VA or MSZ-AP15VF × 2,
PUMY-P140: MSZ-SF15VA or MSZ-AP15VF × 3