49
Check Code
Abnormal points and detection method
Judgment and action
Case
E8
(6840)
Indoor/outdoor unit communication
error (Signal receiving error)
(Outdoor unit)
Abnormal if outdoor controller circuit board
could not receive anything normally for 3
minutes.
1
Contact failure of indoor/
outdoor unit connecting wire
2
Defective communication circuit
of outdoor controller circuit board
3
Defective communication circuit
of indoor controller board
4
Noise has entered into indoor/
outdoor unit connecting wire.
1
Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor or
outdoor units.
2
–
4
Turn the power off, and on again to
check. Replace indoor controller board
or outdoor controller circuit board if
abnormality is displayed again.
E3
or
E5
Remote controller transmission error
(E3)/signal receiving error (E5)
1
Abnormal if remote controller could not
find blank of transmission path for 6
seconds and could not transmit.
(Check code: E3)
2
Remote controller receives transmitted
data at the same time, compares the
data, and when detecting it, judges
different data to be abnormal 30
continuous times. (Check code: E3)
1
Abnormal if indoor controller board could
not find blank of transmission path.
(Check code: E5)
2
Indoor controller board receives
transmitted data at the same time,
compares the data, and when detecting
it, judges different data to be abnormal
30 continuous times. (Check code: E5)
1
Set a remote controller to main, and the
other to sub.
2
Remote controller is connected with only one
indoor unit.
3
The address changes to a separate setting.
4
–
6
Diagnose remote controller.
a) When “RC OK” is displayed, remote
controllers have no problem.
Turn the power off, and on again to check.
When becoming abnormal again, replace
indoor controller board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00-66” is
displayed, noise may be causing
abnormality.
1
2 remote controller are set as
“main.”
(In case of 2 remote controllers)
2
Remote controller is connected
with 2 indoor units or more.
3
Repetition of refrigerant
address
4
Defective transmitting receiving
circuit of remote controller
5
Defective transmitting receiving
circuit of indoor controller board
6
Noise has entered into
transmission wire of remote
controller.
E1
or
E2
Remote controller control board
1
Abnormal if data cannot be normally
read from the nonvolatile memory of the
remote controller control board.
(Check code: E1)
2
Abnormal if the clock function of remote
controller cannot be normally operated.
(Check code: E2)
1
Defective remote controller
1
Replace remote controller.
E6
(6840)
Indoor/outdoor unit communication
error (Signal receiving error)
1
Abnormal if indoor controller board could
not receive any signal normally for 6
minutes after turning the power on.
2
Abnormal if indoor controller board could
not receive any signal normally for 3
minutes.
3
Consider the unit as abnormal under
the following condition. When 2 or more
indoor units are connected to an outdoor
unit, indoor controller board could not
receive a signal for 3 minutes from
outdoor controller circuit board, a signal
which allows outdoor controller circuit
board to transmit signals.
Check LED display on outdoor controller circuit
board. (Connect A-Control service tool (PAC-
SK52ST))
Refer to EA to EC item if LED displays EA to AC.
1
Check disconnecting or looseness of indoor
/outdoor unit connecting wire of indoor unit
or outdoor unit.
Check all the units in case of twin/triple/
quadruple indoor unit system.
2
–
4
Turn the power off, and on again to check.
If abnormality generates again, replace indoor
controller board or outdoor controller circuit
board.
Note: Other indoor controller board may have
defect in the case of twin/triple/quadruple
indoor unit system.
5
Turn the power off, and detach fan motor
from connector (CNF1, 2). Then turn the
power on again.
If abnormality is not displayed, replace fan
motor.
If abnormality is displayed, replace outdoor
controller circuit board.
6
Check the rush current resistor on outdoor
power circuit board with tester. If open is
detected, replace the power circuit board.
1
Contact failure, short circuit or
miswiring (converse wiring) of
indoor/outdoor unit connecting
wire
2
Defective transmitting receiving
circuit of outdoor controller
circuit board.
3
Defective transmitting receiving
circuit of indoor controller
board.
4
Noise has entered into indoor/
outdoor unit connecting wire.
5
Defective fan motor
6
Defective rush current resistor
of outdoor power circuit board
E7
Indoor/outdoor unit communication
error (Transmitting error)
Abnormal if “1” receiving is detected 30
times continuously though indoor controller
board has transmitted “0”.
1
Defective transmitting receiving
circuit of indoor controller board
2
Noise has entered into power
supply.
3
Noise has entered into outdoor
control wire.
1
–
3
Turn the power off, and on again to
check. If abnormality generates again,
replace indoor controller board.
OCH527C