85
<Display function of inspection for outdoor unit>
The blinking patterns of both LED1 (green) and LED2 (red) indicate the types of abnormality when it occurs. Types of
abnormality can be indicated in details by connecting an optional part ‘A-Control Service Tool (PAC-SK52ST)’ to connector
CNM on outdoor controller board.
1
Be sure to replace the 4-way valve.
2
Check refrigerant pipes for disconnection or leakage.
3
After the recovery of refrigerant, vacuum dry the whole
refrigerant circuit.
4
Refer to “11-6. HOW TO CHECK THE PARTS”.
5
Check refrigerant circuit for operation.
F5
—
—
—
E6
E7
—
—
E0
E3
E4
E5
EF
PL
Ed
A0~A8
[Display]
(1)Normal condition
(2)Abnormal condition
Unit condition
Outdoor controller board
A-Control Service Tool
LED1 (Green)
LED2 (Red)
Error code
When the power is turned on
When unit stops
When compressor is warming up
When unit operates
Lighted
Lighted
Lighted
Lighted
Lighted
Not lighted
Indication of the display
Alternately blinking display
Operation mode
Not lighted
Lighted
00, etc.
08, etc.
C5, H7, etc.
Indication
Error
Check
code
*1
Outdoor controller board
Contents
Inspection method
LED1 (Green) LED2 (Red)
1 blinking 2 blinking
2 blinking 1 blinking
2 blinking
3 blinking
4 blinking
5 blinking
Connector (63H) is open.
Startup time over
Check code is not defined.
Miswiring of indoor/outdoor unit conne-
cting wire, excessive number of indoor
units (4 units or more)
Miswiring of indoor/outdoor unit co-
nnecting wire (converse wiring or di-
sconnection)
Indoor/outdoor unit communication error
(signal receiving error) is detected by in-
door unit.
Indoor/outdoor unit communication error
(transmitting error) is detected by indoor
unit.
Indoor/outdoor unit communication error
(signal receiving error) is detected by
outdoor unit.
Indoor/outdoor unit communication error
(transmitting error) is detected by outdoor
unit.
Remote controller signal receiving
error is detected by remote controller.
Remote controller transmitting error
is detected by remote controller.
Remote controller signal receiving
error is detected by indoor unit.
Remote controller transmitting error
is detected by indoor unit.
Serial communication error
<Communication between outdoor
controller board and outdoor power
board>
<Communication between outdoor
controller board and M-NET P.C. board>
Communication error of M-NET
system
*1.Check code displayed on remote controller
1
Check if indoor/outdoor connecting wire is connected correctly.
2
Check if 4 or more indoor units are connected to outdoor unit.
3
Check if noise entered into indoor/outdoor connecting wire
or power supply.
4
Re-check error by turning off power, and on again.
1
Check if connector (63H) on the outdoor controller board is
not disconnected.
2
Check continuity of pressure switch (63H) by tester.
1
Check if connector (CN4) on outdoor controller board and
outdoor power board is not disconnected.
2
Check if there is poor connection of connector on outdoor
controller board(CNMNT and CNVMNT).
3
Check M-NET communication signal.
1
Check if remote controller is MA remote controller(PAR-21MAA).
2
Check if noise entered into transmission wire of remote controller.
3
Check if noise entered into indoor/outdoor connecting wire.
4
Re-check error by turning off power, and on again.
1
Check if connecting wire of indoor unit or remote controller
is connected correctly.
2
Check if noise entered into transmission wire of remote
controller.
3
Re-check error by turning off power, and on again.
1
Check if indoor/outdoor connecting wire is connected correctly.
2
Check if noise entered into indoor/outdoor connecting wire or
power supply.
3
Check if noise entered into indoor/outdoor controller board.
4
Re-check error by turning off power, and on again.
P.42
P.43
(EA)
P.43
(Eb)
P.43
(EC)
P.49
P.49
P.49
(E8)
P.50
(E9)
P.48
P.49
P.48
P.49
P.50
P.51
P.50
P.51~
P.54
Detailed
reference
page
Continue to the next page
OCH527C