![Mitsubishi Electric PUHZ-ZRP100YKAR1 Скачать руководство пользователя страница 94](http://html.mh-extra.com/html/mitsubishi-electric/puhz-zrp100ykar1/puhz-zrp100ykar1_service-manual_1811204094.webp)
94
SW2 setting
Display detail
Explanation for display
Unit
:
0 to 255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 sec. 0.5sec. 2 sec.
Sub cool on error occurring SC
0 to 130
Cooling = TH6−TH3
Heating = TH5−TH2
0 to 130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 sec. 0.5sec. 2 sec.
Thermo-on time until error stops
0 to 999
0 to 999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 sec. 0.5sec. 2 sec.
Indoor pipe temperature / Liquid
(TH2 (3))
Indoor 3
−39 to 88
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
Indoor pipe temperature / Cond./ Eva.
(TH5 (3))
Indoor 3
−39 to 88
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
When there is no indoor unit, “00” is displayed.
50
1
:
1
ON
2 3 4 5 6
Discharge superheat on error occurring
SHd
0 to 255
Cooling = TH4−TH6
Heating = TH4−TH5
Indoor pipe temperature / Liquid
(TH2 (4))
Indoor 4
−39 to 88
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
:
Minute
:
:
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
15
1
15
4
1
ON
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva
(TH5 (4))
Indoor 4
−39 to 88
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
When there is no indoor unit, “00” is displayed.
:
The black square ( ) indicates a switch position.
OCH527C