6.2. Field electrical wiring

Outdoor unit model

RP71V

RP100,15V

RP140, 170V

RP100, 15, 140Y

RP170, 00Y

Outdoor unit power supply

~/N (single), 50 Hz, 30 V ~/N (single), 50 Hz, 30 V ~/N (single), 50 Hz, 30 V

3N~ (3 ph 4-wires), 

50 Hz, 400 V

3N~ (3 ph 4-wires), 

50 Hz, 400 V

Outdoor unit input capacity Main switch (Breaker)

*1

5 A

3 A

40 A

16 A

3 A

Wiring 

Wire No. × 

size (mm

) Outdoor unit power supply

3 × Min. .5

3 × Min. 4

3 × Min. 6

5 × Min. 1.5

5 × Min. 4

Indoor unit-Outdoor unit

*

3 × 1.5 (Polar)

3 × 1.5 (Polar)

3 × 1.5 (Polar)

3 × 1.5 (Polar)

Cable length 50m:3×4(Polar)/Cable 

length 80m:3×6(Polar)

Indoor unit-Outdoor unit earth

*

1 × Min. 1.5

1 × Min. 1.5

1 × Min. 1.5

1 × Min. 1.5

1 × Min. .5

Remote controller-Indoor unit

*3

 × 0.3 (Non-polar)

 × 0.3 (Non-polar)

 × 0.3 (Non-polar)

 × 0.3 (Non-polar)

 × 0.3 (Non-polar)

Circuit rating

Outdoor unit L-N (single)
Outdoor unit L1-N, L-N, L3-N (3 phase)

*4

AC 30 V

AC 30 V

AC 30 V

AC 30 V

AC 30 V

Indoor unit-Outdoor unit S1-S

*4

AC 30 V

AC 30 V

AC 30 V

AC 30 V

AC 30 V

Indoor unit-Outdoor unit S-S3

*4

DC 4 V

DC 4 V

DC 4 V

DC 4 V

DC 4 V

Remote controller-Indoor unit

*4

DC 1 V

DC 1 V

DC 1 V

DC 1 V

DC 1 V

*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
*. (RP71-140)
  Max. 45 m
  If .5 mm

 used, Max. 50 m

  If .5 mm

 used and S3 separated, Max. 80 m

  (RP170, 00)
  Max. 80 m Total Max. including all indoor/indoor connection is 80 m.

• Use one cable for S1 and S and another for S3 as shown in the picture.
• Max. 50 m Total Max. for PEA. Wiring size 3 × 1.5 (Polar).

*3. The 10 m wire is attached in the remote controller accessory.

*4.  The figures are NOT always against the ground.

  S3 terminal has DC 4 V against S terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.

Notes:  1.  Wiring size must comply with the applicable local and national code.

      2. 

Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)

      3.  Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied.

A-Control 

Outdoor Unit

3 poles isolator

Power supply

Isolator

A-Control 

Indoor Unit

 Warning:

·   In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between 

power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when 

the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.

6. Electrical work

INDOOR-OUTDOOR CONNECTING CABLE (RP170,200) 

Cross section of cable

Wire size (mm

2

)

Number of wires

Polarity

L (m)*6

Round

2.5

3

Clockwise : S1-S2-S3

*Pay attention to stripe of yellow and green

(30)

*2

Flat

2.5

3

Not applicable

(Because center wire has no cover finish)

Not applicable

*5

Flat

1.5

4

From left to right : S1-Open-S2-S3

(18)

*3

Round

2.5

4

Clockwise : S1-S2-S3-Open

*Connect S1 nad S3 to the opposite angle

(30)

*4

*1 :Power supply cords of appliances shall not be lighter than design 60245 IEC or

     227 IEC.
*2 :In case that cable with stripe of yellow and green is available.

*3 :In case of regular polarity connection (S1-S2-S3), wire size is 1.5 mm

2.

*4 :In case of regular polarity connection (S1-S2-S3).

*5 :In the flat cables are connected as this picture, they can be used up to 30 m.

*6 :Mentioned cable length is just a reference value.

     It may be different depending on the condition of installation, humidity or 

     materials, etc.

(3C Flat cable × 2)

Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).

Intermediate connections can lead to communication error if water enters the cables and causes insufficient insulation to ground or a poor electrical contact at the inter-

mediate connection point.

S1

S3

S2

Never splice the power cable or the indoor-outdoor connection cable, otherwise it may result in a smoke, a fire or communication failure.

Содержание PUHZ-RP HA5

Страница 1: ...ALLER Air Conditioners PUHZ RP HA5 PUHZ RP KA2 INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit English ...

Страница 2: ...ult a dealer for repairs If alterations or repairs are not performed correctly water leakage electric shock or fire may re sult The user should never attempt to repair the unit or transfer it to another location If the unit is installed incorrectly water leakage electric shock or fire may result If the air conditioner must be repaired or moved ask a dealer or an authorized technician After install...

Страница 3: ...essary to use R410A refrigerant Contact your nearest dealer for any questions Tools for R410A Gauge manifold Flare tool Charge hose Size adjustment gauge Gas leak detector Vacuum pump adapter Torque wrench Electronic refrigerant charging scale Be sure to use the correct tools If dust debris or moisture enters the re frigerant lines refrigeration oil deterioration may result Do not use a charging c...

Страница 4: ...t be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for RP100 200 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for RP100 200 models is 1000 mm or more 5 Singl...

Страница 5: ...es that use R410A refrigerant Refer to 1 5 for precautions not included below on using air conditioners with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thicknesses specified in the...

Страница 6: ...ersed refrigerant leak occurs because of the part damaging by brazing fire For PEA RP170 200WHA The method of pipe connection is brazing connection PEA 170 PEA 200 Gas side Pipe size mm 25 4 25 4 Liquid side Pipe size mm 9 52 9 52 4 Installing the refrigerant piping Fig 4 4 A Front piping cover B Piping cover C Stop valve D Service panel E Bend radius 100 mm 150 mm 4 3 Refrigerant piping Fig 4 4 R...

Страница 7: ...pipe cover following the groove and wrap the pipes Pipe inlet gap for RP71 200 Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re main If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result 4 6 Addition of refrigerant Additional charging is not necessary if the pipe length does not exceed 30 m If the pipe length e...

Страница 8: ... 2 t1 0 50m 20m 25 4 t1 0 50m 20m 22 2 t1 0 40m 20m 25 4 t1 0 40m 20m 28 58 t1 0 40m 20m 28 58 t1 0 50m 20m 31 75 t1 1 40m 20m RP170 200 Additional refrigerant amount when the liquid pipe of the larger diameter is used 1 1 system Liquid pipe When the pipe length exceeds 20 m 15 88 Additional refrigerant amount w g 180 Pipe length m 3000 w g 0 Additional charge is not necessary Simultaneous twin tr...

Страница 9: ...s not meet specifications or the pipes are damaged Fig 4 9 4 8 For twin triple combination Fig 4 9 When this unit is used as a FREE COMPO MULTI unit install the refrigerant piping with the restrictions indicated in the drawing on the left In addition if the restrictions are going to be exceeded or if there are going to be combinations of indoor and outdoor units refer to installation instructions ...

Страница 10: ...ove the service panel 2 Wire the cables referring to the Fig 6 1 and the Fig 6 2 Except PEA RP170 200WHA C Fig 6 1 A Indoor unit B Outdoor unit C Remote controller D Main switch Breaker E Earth Fig 6 2 A B D D A A A B C E E E E For Power For Power L N S1 S2 S3 RP71 170V L1 L2 L3 N S1 S2 S3 RP100 200Y F Terminal block G Indoor Outdoor connection terminal block S1 S2 S3 H Service panel I Clamp Clamp...

Страница 11: ...ng cords shall not be lighter than polychloroprene sheathed flexible cord Design 60245 IEC 57 3 Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied A Control Outdoor Unit 3 poles isolator Power supply Isolator A Control Indoor Unit Warning In case of A control wiring there is high voltage potential on the S3 terminal caused by elec...

Страница 12: ... accumulated in the compressor the compressor must be warmed up at least 12 hours to prevent breakdown 4 If the insulation resistance rises above 1 M the compressor is not faulty Caution The compressor will not operate unless the power supply phase connec tion is correct Turn on the power at least 12 hours before starting operation Starting operation immediately after turning on the main power swi...

Страница 13: ...of the outdoor unit can be reduced by about 3 4 dB The low noise mode will be activated when a commercially available timer or the contact input of an ON OFF switch is added to the CNDM connector option on the control board of the outdoor unit The ability varies according to the outdoor temperature and conditions etc 1 Complete the circuit as shown when using the external input adapter PAC SC36NA ...

Страница 14: ...ayed the refrigerant collecting pump down cannot be completed normally 2 After the gas stop valve is closed set the SWP switch on the control board of the outdoor unit to ON The compressor outdoor unit and ventilators indoor and outdoor units start operating and refrigerant collecting operation begins LED1 and LED2 on the control board of the outdoor unit are lit Only set the SWP switch push butto...

Страница 15: ...Fig 2 6 1 5 0 1 0 0 3 0 0 2 0 0 1000 Max 500 200 100 200 100 300 1000 500 150 100 1000 500 2 5 0 1 5 0 1500 1000 500 300 Max 500 300 200 1500 1000 500 300 1500 1000 Max 300 1500 1000 1500 1000 5 0 0 3 0 0 1000 500 600 400 2000 1000 150 100 1500 1000 600 400 3000 2000 500 300 1 5 0 0 1 0 0 0 800 500 150 2 5 0 1 5 0 ...

Страница 16: ... OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN RG79U640L02 Printed in Japan This product is designed and intended for use in the residential commercial and light industrial environment ...

Отзывы: