background image

7

4. Installing the refrigerant piping

A

A

  Stop valve <Liquid side>

B

  Stop valve <Gas side>

C

  Service port

D

  Open/Close section

E

  Local pipe

F

  Sealed, same way for gas side

G

  Pipe cover

Do not use a wrench here.

     Refrigerant leakage may result.

Use  wrenches here.

D

B

C

G

F

E

D

C

A

Fig. 4-5

Fig. 4-6

Fig. 4-7

4.4. Refrigerant pipe airtight testing method (Fig. 4-5)

(1) Connect the testing tools.

  •   Make sure the stop valves 

A

 

B

 are closed and do not open them.

  •   Add pressure to the refrigerant lines through the service port 

C

 of the liquid 

stop valve 

A

.

()

  Do not add pressure to the specified pressure all at once; add pressure little by 

little.

 

1

  Pressurize to 0.5 MPa (5 kgf/cm

G), wait 5 minutes, and make sure the pres-

sure does not decrease.

 

2

  Pressurize to 1.5 MPa (15 kgf/cm

G), wait 5 minutes, and make sure the 

pressure does not decrease.

 

3

  Pressurize to 4.15 MPa (41.5 kgf/cm

G) and measure the surrounding tem-

perature and refrigerant pressure.

(3)

  If the specified pressure holds for about one day and does not decrease, the 

pipes have passed the test and there are no leaks.

  •   If the surrounding temperature changes by 1 °C, the pressure will change by 

about 0.01 MPa (0.1 kgf/cm

G). Make the necessary corrections.

(4)  If the pressure decreases in steps () or (3), there is a gas leak. Look for the 

source of the gas leak.

4.5. Stop valve opening method

The stop valve opening method varies according to the outdoor unit model. Use the 

appropriate method to open the stop valves.

(1) Gas side of RP100 - 00 (Fig. 4-6)

1

  Remove the cap, pull the handle toward you and rotate 1/4 turn in a counter-

clockwise direction to open.

2

  Make sure that the stop valve is open completely, push in the handle and rotate 

the cap back to its original position.

() Liquid side of RP100 - 00 and Gas/Liquid side of RP71 (Fig. 4-7)

1

  Remove the cap and turn the valve rod counterclockwise as far as it will go with 

the use of a 4 mm hexagonal wrench. Stop turning when it hits the stopper.

   (ø9.5: Approximately 10 revolutions)

2

  Make sure that the stop valve is open completely, push in the handle and rotate 

the cap back to its original position.

Refrigerant pipes are protectively wrapped for RP71 - 00

•   The pipes can be protectively wrapped up to a diameter of ø90 before or after 

connecting the pipes. Cut out the knockout in the pipe cover following the groove 

and wrap the pipes. 

Pipe inlet gap for RP71 - 00

•   Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re-

main. (If the gaps are not closed, noise may be emitted or water and dust will 

enter the unit and breakdown may result.)

4.6. Addition of refrigerant

•   Additional charging is not necessary if the pipe length does not exceed 30 m.

•   If the pipe length exceeds 30 m, charge the unit with additional R410A refriger-

ant according to the permitted pipe lengths in the chart below.

  *   When the unit is stopped, charge the unit with the additional refrigerant 

through the liquid stop valve after the pipe extensions and indoor unit have 

been vacuumized.

     When the unit is operating, add refrigerant to the gas check valve using a 

safety charger. Do not add liquid refrigerant directly to the check valve.

  *   After charging the unit with refrigerant, note the added refrigerant amount on 

the service label (attached to the unit).

     Refer to the “1.5. Using R410A refrigerant air conditioners” for more informa-

tion.

•   Be careful when installing multiple units. Connecting to an incorrect indoor unit 

can lead to abnormally high pressure and have a serious effect on operation 

performance.

Model

Permitted 

pipe  

length

Permitted 

vertical  

difference

Additional refrigerant charging amount

31 - 40 m 41 - 50 m 51 - 60 m 61 - 70 m  - 75 m

RP71

- 50 m

- 30 m

0.6 kg 1. kg

RP100 - 140

- 75 m

0.6 kg 1. kg 1.8 kg

.4 kg

RP170 - 00

- 75 m

0.9 kg 1.8 kg .4 kg 3.6 kg 4.5 kg

I

  Double spanner section

   (Do not apply a spanner other than to this section. 

Doing so would cause coolant leaks.)

J

  Seal section

   (Seal the end of the heat insulation material at 

the pipe connection section with whatever seal 
material you have on hand so that water does not 

infiltrate the heat insulation material.)

A

  Valve

B

  Unit side

C

  Handle

Cap

E

  Local pipe side

F

  Pipe cover

G

  Service port

H

  Wrench hole

I

H

B

Precautions when using the charge valve (Fig.4-8)

Do not tighten the service port too much when installing it, otherwise, the valve core

could be deformed and become loose, causing a gas leak.

After positioning section 

B

 in the desired direction, turn section 

A

 only and tighten it.

Do not further tighten sections 

A

 and 

B

 together after tightening section 

A

.

* The figure to the left is an example only.

  The stop valve shape, service port position,
  etc., may vary according to the model.
* Turn section 

A

 only.

  (Do not further tighten sections 

A

 and 

B

   together.)

C

 Charge hose

D

 Service port

A

B

C

D

Fig. 4-8

(1)

(2)

Содержание PUHZ-RP HA5

Страница 1: ...ALLER Air Conditioners PUHZ RP HA5 PUHZ RP KA2 INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit English ...

Страница 2: ...ult a dealer for repairs If alterations or repairs are not performed correctly water leakage electric shock or fire may re sult The user should never attempt to repair the unit or transfer it to another location If the unit is installed incorrectly water leakage electric shock or fire may result If the air conditioner must be repaired or moved ask a dealer or an authorized technician After install...

Страница 3: ...essary to use R410A refrigerant Contact your nearest dealer for any questions Tools for R410A Gauge manifold Flare tool Charge hose Size adjustment gauge Gas leak detector Vacuum pump adapter Torque wrench Electronic refrigerant charging scale Be sure to use the correct tools If dust debris or moisture enters the re frigerant lines refrigeration oil deterioration may result Do not use a charging c...

Страница 4: ...t be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for RP100 200 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for RP100 200 models is 1000 mm or more 5 Singl...

Страница 5: ...es that use R410A refrigerant Refer to 1 5 for precautions not included below on using air conditioners with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thicknesses specified in the...

Страница 6: ...ersed refrigerant leak occurs because of the part damaging by brazing fire For PEA RP170 200WHA The method of pipe connection is brazing connection PEA 170 PEA 200 Gas side Pipe size mm 25 4 25 4 Liquid side Pipe size mm 9 52 9 52 4 Installing the refrigerant piping Fig 4 4 A Front piping cover B Piping cover C Stop valve D Service panel E Bend radius 100 mm 150 mm 4 3 Refrigerant piping Fig 4 4 R...

Страница 7: ...pipe cover following the groove and wrap the pipes Pipe inlet gap for RP71 200 Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re main If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result 4 6 Addition of refrigerant Additional charging is not necessary if the pipe length does not exceed 30 m If the pipe length e...

Страница 8: ... 2 t1 0 50m 20m 25 4 t1 0 50m 20m 22 2 t1 0 40m 20m 25 4 t1 0 40m 20m 28 58 t1 0 40m 20m 28 58 t1 0 50m 20m 31 75 t1 1 40m 20m RP170 200 Additional refrigerant amount when the liquid pipe of the larger diameter is used 1 1 system Liquid pipe When the pipe length exceeds 20 m 15 88 Additional refrigerant amount w g 180 Pipe length m 3000 w g 0 Additional charge is not necessary Simultaneous twin tr...

Страница 9: ...s not meet specifications or the pipes are damaged Fig 4 9 4 8 For twin triple combination Fig 4 9 When this unit is used as a FREE COMPO MULTI unit install the refrigerant piping with the restrictions indicated in the drawing on the left In addition if the restrictions are going to be exceeded or if there are going to be combinations of indoor and outdoor units refer to installation instructions ...

Страница 10: ...ove the service panel 2 Wire the cables referring to the Fig 6 1 and the Fig 6 2 Except PEA RP170 200WHA C Fig 6 1 A Indoor unit B Outdoor unit C Remote controller D Main switch Breaker E Earth Fig 6 2 A B D D A A A B C E E E E For Power For Power L N S1 S2 S3 RP71 170V L1 L2 L3 N S1 S2 S3 RP100 200Y F Terminal block G Indoor Outdoor connection terminal block S1 S2 S3 H Service panel I Clamp Clamp...

Страница 11: ...ng cords shall not be lighter than polychloroprene sheathed flexible cord Design 60245 IEC 57 3 Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied A Control Outdoor Unit 3 poles isolator Power supply Isolator A Control Indoor Unit Warning In case of A control wiring there is high voltage potential on the S3 terminal caused by elec...

Страница 12: ... accumulated in the compressor the compressor must be warmed up at least 12 hours to prevent breakdown 4 If the insulation resistance rises above 1 M the compressor is not faulty Caution The compressor will not operate unless the power supply phase connec tion is correct Turn on the power at least 12 hours before starting operation Starting operation immediately after turning on the main power swi...

Страница 13: ...of the outdoor unit can be reduced by about 3 4 dB The low noise mode will be activated when a commercially available timer or the contact input of an ON OFF switch is added to the CNDM connector option on the control board of the outdoor unit The ability varies according to the outdoor temperature and conditions etc 1 Complete the circuit as shown when using the external input adapter PAC SC36NA ...

Страница 14: ...ayed the refrigerant collecting pump down cannot be completed normally 2 After the gas stop valve is closed set the SWP switch on the control board of the outdoor unit to ON The compressor outdoor unit and ventilators indoor and outdoor units start operating and refrigerant collecting operation begins LED1 and LED2 on the control board of the outdoor unit are lit Only set the SWP switch push butto...

Страница 15: ...Fig 2 6 1 5 0 1 0 0 3 0 0 2 0 0 1000 Max 500 200 100 200 100 300 1000 500 150 100 1000 500 2 5 0 1 5 0 1500 1000 500 300 Max 500 300 200 1500 1000 500 300 1500 1000 Max 300 1500 1000 1500 1000 5 0 0 3 0 0 1000 500 600 400 2000 1000 150 100 1500 1000 600 400 3000 2000 500 300 1 5 0 0 1 0 0 0 800 500 150 2 5 0 1 5 0 ...

Страница 16: ... OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN RG79U640L02 Printed in Japan This product is designed and intended for use in the residential commercial and light industrial environment ...

Отзывы: