Mitsubishi Electric PUHZ-RP HA5 Скачать руководство пользователя страница 6

90

°

±

0.5

°

øA

R0.4~R0.8

45

°±

 2

 °

90

°

±

0.5

°

øA

R0.4~R0.8

45

°±

 2

 °

6

4.2. Connecting pipes (Fig. 4-1)

•   When commercially available copper pipes are used, wrap liquid and gas pipes 

with commercially available insulation materials (heat-resistant to 100 °C or 

more, thickness of 1 mm or more).

•   The indoor parts of the drain pipe should be wrapped with polyethylene foam 

insulation materials (specific gravity of 0.03, thickness of 9 mm or more).

•   Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten-

ing flare nut. 

A

•   Use  wrenches to tighten piping connections. 

B

•   Use leak detector or soapy water to check for gas leaks after connections are 

completed.

•   Apply refrigerating machine oil over the entire flare seat surface. 

C

•   Use the flare nuts for the following pipe size. 

D

RP71

RP100 - 140 RP170,00

Gas side

Pipe size (mm)

[

15.88

[

15.88

[

5.4

Liquid side Pipe size (mm)

[

9.5

[

9.5

[

9.5

•   When bending the pipes, be careful not to break them. Bend radii of 100 mm to 

150 mm are sufficient.

•   Make sure the pipes do not contact the compressor. Abnormal noise or vibration 

may result.

1

 Pipes must be connected starting from the indoor unit.

  Flare nuts must be tightened with a torque wrench.

2

  Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil (Ap-

plied on site).

•   When usual pipe sealing is used, refer to Table 1 for flaring of R410A refrigerant 

pipes.

  The size adjustment gauge can be used to confirm A measurements.

A

 (Fig. 4-1)

Copper pipe O.D.

(mm)

Flare dimensions

øA dimensions (mm)

ø6.35

8.7 - 9.1

ø9.5

1.8 - 13.

ø1.7

16. - 16.6

ø15.88

19.3 - 19.7

ø19.05

3.6 - 4.0

B

 (Fig. 4-1)

Copper pipe O.D.  

(mm)

Flare nut O.D.  

(mm)

Tightening torque  

(N·m)

ø6.35

17

14 - 18

ø6.35

34 - 4

ø9.5

34 - 4

ø1.7

6

49 - 61

ø1.7

9

68 - 8

ø15.88

9

68 - 8

ø15.88

36

100 - 10

ø19.05

36

100 - 10

A

  Flare cutting dimensions

B

  Flare nut tightening torque

A

B

C

D

A

  Die

B

  Copper pipe

A

B

Fig. 4-1

Fig. 4-2

A

Table 1 (Fig. 4-)

Copper pipe O.D. 

(mm)

A (mm)

Flare tool for R410A

Flare tool for R·R407C

Clutch type

ø6.35 (1/4")

0 - 0.5

1.0 - 1.5

ø9.5 (3/8")

0 - 0.5

1.0 - 1.5

ø1.7 (1/")

0 - 0.5

1.0 - 1.5

ø15.88 (5/8")

0 - 0.5

1.0 - 1.5

ø19.05 (3/4")

0 - 0.5

1.0 - 1.5

3

 Use the following procedure for connecting the gas-side piping. (Fig.4-3) (RP170 / 00)

1  Braze the 

E

 Joint pipe provided to the outdoor unit using locally procured braz-

ing materials and 

C

 Local piping without oxygen.

  Connect the 

E

 Joint pipe to the gas-side Stop valve.

    Use 2 wrenches to tighten the flare nut.

     * If order is reversed, refrigerant leak occurs because of the part damaging by 

brazing fire.

• For PEA-RP170, 00WHA

  The method of pipe connection is brazing connection.

PEA-170

PEA-00

Gas side

Pipe size (mm)

[

5.4

[

5.4

Liquid side Pipe size (mm)

[

9.5

[

9.5

4. Installing the refrigerant piping

Fig. 4-4

A

 Front piping cover

B

 Piping cover

C

 Stop valve

D

 Service panel

E

 Bend radius : 100 mm - 150 mm

4.3. Refrigerant piping (Fig. 4-4)

Remove the service panel 

D

 (3 screws) and the front piping cover 

A

 ( screws) 

and rear piping cover 

B

 ( screws: RP71) (4 screws: RP100 - 00).

1

  Perform refrigerant piping connections for the indoor/outdoor unit when the out-

door unit’s stop valve is completely closed.

2

  Vacuum-purge air from the indoor unit and the connection piping.

3

  After connecting the refrigerant pipes, check the connected pipes and the indoor 

unit for gas leaks. (Refer to 4.4 Refrigerant pipe airtight testing method)

4

  A high-performance vacuum pump is used at the stop valve service port to main-

tain a vacuum for an adequate time (at least one hour after reaching –101 kPa 

(5 Torr)) in order to vacuum dry the inside of the pipes. Always check the degree 

of vacuum at the gauge manifold. If there is any moisture left in the pipe, the de-

gree of vacuum is sometimes not reached with short-time vacuum application. 

   After vacuum drying, completely open the stop valves (both liquid and gas) for 

the outdoor unit. This completely links the indoor and outdoor refrigerant circuits.

  •   If the vacuum drying is inadequate, air and water vapor remain in the refriger-

ant circuits and can cause abnormal rise of high pressure, abnormal drop of 

low pressure, deterioration of the refrigerating machine oil due to moisture, etc.

  •   If the stop valves are left closed and the unit is operated, the compressor and 

control valves will be damaged.

  •   Use a leak detector or soapy water to check for gas leaks at the pipe connec-

tion sections of the outdoor unit.

  •   Do not use the refrigerant from the unit to purge air from the refrigerant lines.

  •   After the valve work is completed, tighten the valve caps to the correct torque: 

0 to 5 N·m (00 to 50 kgf·cm).

     Failure to replace and tighten the caps may result in refrigerant leakage. In 

addition, do not damage the insides of the valve caps as they act as a seal to 

prevent refrigerant leakage.

5

  Use sealant to seal the ends of the thermal insulation around the pipe connec-

tion sections to prevent water from entering the thermal insulation.

Fig. 4-3

A

 Stop valve

B

 Seal section

C

 Local piping

D

 Double spanner section

E

 Joint pipe

F

 Pipe cover

 Warning:

When installing the unit, securely connect the refrigerant pipes before start

-

ing the compressor.

Содержание PUHZ-RP HA5

Страница 1: ...ALLER Air Conditioners PUHZ RP HA5 PUHZ RP KA2 INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit English ...

Страница 2: ...ult a dealer for repairs If alterations or repairs are not performed correctly water leakage electric shock or fire may re sult The user should never attempt to repair the unit or transfer it to another location If the unit is installed incorrectly water leakage electric shock or fire may result If the air conditioner must be repaired or moved ask a dealer or an authorized technician After install...

Страница 3: ...essary to use R410A refrigerant Contact your nearest dealer for any questions Tools for R410A Gauge manifold Flare tool Charge hose Size adjustment gauge Gas leak detector Vacuum pump adapter Torque wrench Electronic refrigerant charging scale Be sure to use the correct tools If dust debris or moisture enters the re frigerant lines refrigeration oil deterioration may result Do not use a charging c...

Страница 4: ...t be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for RP100 200 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for RP100 200 models is 1000 mm or more 5 Singl...

Страница 5: ...es that use R410A refrigerant Refer to 1 5 for precautions not included below on using air conditioners with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thicknesses specified in the...

Страница 6: ...ersed refrigerant leak occurs because of the part damaging by brazing fire For PEA RP170 200WHA The method of pipe connection is brazing connection PEA 170 PEA 200 Gas side Pipe size mm 25 4 25 4 Liquid side Pipe size mm 9 52 9 52 4 Installing the refrigerant piping Fig 4 4 A Front piping cover B Piping cover C Stop valve D Service panel E Bend radius 100 mm 150 mm 4 3 Refrigerant piping Fig 4 4 R...

Страница 7: ...pipe cover following the groove and wrap the pipes Pipe inlet gap for RP71 200 Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re main If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result 4 6 Addition of refrigerant Additional charging is not necessary if the pipe length does not exceed 30 m If the pipe length e...

Страница 8: ... 2 t1 0 50m 20m 25 4 t1 0 50m 20m 22 2 t1 0 40m 20m 25 4 t1 0 40m 20m 28 58 t1 0 40m 20m 28 58 t1 0 50m 20m 31 75 t1 1 40m 20m RP170 200 Additional refrigerant amount when the liquid pipe of the larger diameter is used 1 1 system Liquid pipe When the pipe length exceeds 20 m 15 88 Additional refrigerant amount w g 180 Pipe length m 3000 w g 0 Additional charge is not necessary Simultaneous twin tr...

Страница 9: ...s not meet specifications or the pipes are damaged Fig 4 9 4 8 For twin triple combination Fig 4 9 When this unit is used as a FREE COMPO MULTI unit install the refrigerant piping with the restrictions indicated in the drawing on the left In addition if the restrictions are going to be exceeded or if there are going to be combinations of indoor and outdoor units refer to installation instructions ...

Страница 10: ...ove the service panel 2 Wire the cables referring to the Fig 6 1 and the Fig 6 2 Except PEA RP170 200WHA C Fig 6 1 A Indoor unit B Outdoor unit C Remote controller D Main switch Breaker E Earth Fig 6 2 A B D D A A A B C E E E E For Power For Power L N S1 S2 S3 RP71 170V L1 L2 L3 N S1 S2 S3 RP100 200Y F Terminal block G Indoor Outdoor connection terminal block S1 S2 S3 H Service panel I Clamp Clamp...

Страница 11: ...ng cords shall not be lighter than polychloroprene sheathed flexible cord Design 60245 IEC 57 3 Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied A Control Outdoor Unit 3 poles isolator Power supply Isolator A Control Indoor Unit Warning In case of A control wiring there is high voltage potential on the S3 terminal caused by elec...

Страница 12: ... accumulated in the compressor the compressor must be warmed up at least 12 hours to prevent breakdown 4 If the insulation resistance rises above 1 M the compressor is not faulty Caution The compressor will not operate unless the power supply phase connec tion is correct Turn on the power at least 12 hours before starting operation Starting operation immediately after turning on the main power swi...

Страница 13: ...of the outdoor unit can be reduced by about 3 4 dB The low noise mode will be activated when a commercially available timer or the contact input of an ON OFF switch is added to the CNDM connector option on the control board of the outdoor unit The ability varies according to the outdoor temperature and conditions etc 1 Complete the circuit as shown when using the external input adapter PAC SC36NA ...

Страница 14: ...ayed the refrigerant collecting pump down cannot be completed normally 2 After the gas stop valve is closed set the SWP switch on the control board of the outdoor unit to ON The compressor outdoor unit and ventilators indoor and outdoor units start operating and refrigerant collecting operation begins LED1 and LED2 on the control board of the outdoor unit are lit Only set the SWP switch push butto...

Страница 15: ...Fig 2 6 1 5 0 1 0 0 3 0 0 2 0 0 1000 Max 500 200 100 200 100 300 1000 500 150 100 1000 500 2 5 0 1 5 0 1500 1000 500 300 Max 500 300 200 1500 1000 500 300 1500 1000 Max 300 1500 1000 1500 1000 5 0 0 3 0 0 1000 500 600 400 2000 1000 150 100 1500 1000 600 400 3000 2000 500 300 1 5 0 0 1 0 0 0 800 500 150 2 5 0 1 5 0 ...

Страница 16: ... OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN RG79U640L02 Printed in Japan This product is designed and intended for use in the residential commercial and light industrial environment ...

Отзывы: