10
6. Electrical work
Fig. 6-3
* In case of PEA-170, 200
PUHZ-170, 200
PEA-170, 200
Power supply
Earth leakage breaker
Circuit breaker or local switch
LCD remote controller
Outdoor unit
Indoor unit
Power cable wiring
Indoor/outdoor connection wiring
Grounding
* In case of PEA-170, 200
Main remote controller
Subordinate remote controller
Standard (Refrigerant address = 00)
Refrigerant address = 01
!
Refrigerant address = 02
"
Refrigerant address = 15
!
"
6.1. Outdoor unit (Fig. 6-1, Fig. 6-2)
1
Remove the service panel.
2
Wire the cables referring to the Fig. 6-1 and the Fig. 6-.
* Except PEA-RP170, 00WHA
C
Fig. 6-1
A
Indoor unit
B
Outdoor unit
C
Remote controller
D
Main switch (Breaker)
E
Earth
Fig. 6-2
A
B
D
D
A
A
A
B
C
E
E
E
E
For Power
For Power
L N
S1 S2 S3
RP71-170V
L1 L2 L3 N
S1 S2 S3
RP100-200Y
F
Terminal block
G
Indoor/Outdoor connection terminal block (S1, S, S3)
H
Service panel
I
Clamp
* Clamp the cables so that they do not contact the center of the service panel or the gas valve.
J
Earth terminal
Note :
If the protective sheet for the electrical box is removed during servicing, be sure to
reinstall it.
Caution:
Be sure to install N-Line. Without N-Line, it could cause damage to the unit.