Parts name
Checkpoints
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10 to 30°C)
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20°C)
Thermistor (TH3)
<Liquid>
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
<2-phase pipe>
Thermistor (TH7)
<Ambient>
Thermistor (TH8)
<Heatsink>
Thermistor (TH33)
<Comp. surface>
Normal
160 to 410 k
Ω
4.3 to 9.6 k
Ω
39 to 105 k
Ω
TH4, TH33
TH3
TH6
TH7
TH8
Abnormal
Open or short
Normal
Red - White
Red - Orange
Brown - Yellow
Brown - Blue
Abnormal
46 ± 4
"
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20°C)
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20°C)
Solenoid valve coil
<4-way valve>
(21S4)
Solenoid valve coil
(SV1, SV2)
Motor for compressor
(MC)
Linear expansion valve
(LEV-A/LEV-B/LEV-C)
Normal
Abnormal
Open or short
Abnormal
Open or short
Refer to “5-2. COMPRESSOR TECHNICAL DATA”.
Open or short
Refer to next page.
Fan motor (MF1)
2350 ± 170
"
Normal
Abnormal
Open or short
1567 ± 150
"
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20°C)
Solenoid valve coil
(SV3)
Normal
Abnormal
Open or short
1450 ± 150
"
Measure the resistance between the terminals with a tester.
(Winding temperature 20°C)
Normal
W
V
U
Red
Brown
Blue
Orange
Yellow
White
10-6. HOW TO CHECK THE PARTS
PUHZ-FRP71VHA2