Check Code
Abnormal points and detection method
Judgment and action
E9
(6841)
Indoor/outdoor unit communication
error (Transmitting error) (Outdoor unit)
Abnormal if “0” receiving is detected 30
times continuously though outdoor control-
ler circuit board has transmitted “1”.
Abnormal if outdoor controller circuit board
could not find blank of transmission path
for 3 minutes.
1
Indoor/ outdoor unit connecting
wire has contact failure.
2
Defective communication cir-
cuit of outdoor controller circuit
board
3
Noise has entered power supply.
4
Noise has entered indoor/ out-
door unit connecting wire.
1
Check disconnection or looseness of indoor/
outdoor unit connecting wire.
2
–
4
Turn the power off, and on again to
check. Replace outdoor controller circuit
board if abnormality is displayed again.
Cause
E8
(6843)
Indoor/outdoor unit communication
error (Signal receiving error)
(Outdoor unit)
Abnormal if outdoor controller circuit board
could not receive anything normally for 3
minutes.
1
Contact failure of indoor/
outdoor unit connecting wire
2
Defective communication circuit
of outdoor controller circuit
board
3
Defective communication circuit
of indoor controller board
4
Noise has entered into indoor/
outdoor unit connecting wire.
1
Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor or
outdoor units.
2
–
4
Turn the power off, and on again to
check. Replace indoor controller board
or outdoor controller circuit board if
abnormality is displayed again.
E6
(6840)
Indoor/outdoor unit communication
error (Signal receiving error)
Abnormal if indoor controller board could
not receive any signal normally for 6
minutes after turning the power on.
Abnormal if indoor controller board could
not receive any signal normally for 3
minutes.
Consider the unit as abnormal under the
following condition. When 2 or more indoor
units are connected to an outdoor unit,
indoor controller board could not receive a
signal for 3 minutes from outdoor controller
circuit board, a signal which allows outdoor
controller circuit board to transmit signals.
Note: Check LED display on outdoor controller
circuit board. (Connect A-Control service
tool (PAC-SK52ST))
Refer to EA–EC item if LED displays EA–AC.
1
Check disconnecting or looseness of indoor
/outdoor unit connecting wire of indoor unit
or outdoor unit.
Check all the units in the case of twin/triple/
quadruple indoor unit system.
2
–
4
Turn the power off, and on again to check.
If abnormality occurs again, replace indoor
controller board or outdoor controller circuit
board.
Note: Other indoor controller board may
have defect in the case of twin/triple/
quadruple indoor unit system.
5
Turn the power off, and detach fan motor
from connector. Then turn the power on
again.
If abnormality is not displayed, replace fan
motor.
If abnormality is displayed, replace outdoor
controller circuit board.
6
Check the rush current resistor on outdoor
power circuit board with tester. If open is
detected, replace the power circuit board.
1
Contact failure, short circuit or
miswiring (reverse wiring) of
indoor/outdoor unit connecting
wire
2
Defective transmitting receiving
circuit of outdoor controller
circuit board.
3
Defective transmitting receiving
circuit of indoor controller
board.
4
Noise has entered into indoor/
outdoor unit connecting wire.
5
Defective fan motor
6
Defective rush current resistor
of outdoor power circuit board
E7
(6842)
Indoor/outdoor unit communication
error (Transmitting error)
Abnormal if “1” receiving is detected 30
times continuously though indoor controller
board has transmitted “0”.
1
Defective transmitting receiving
circuit of indoor controller board
2
Noise has entered into power
supply.
3
Noise has entered into outdoor
control wire.
1
-
3
Turn the power off, and on again to check.
If abnormality occurs again, replace indoor
controller board.
EE
(7130)
Reverse connection of ATA/ATW com-
munication wire
Abnormal if communication wire of ATA
side and FTC side are connected in
reverse.
1
Each S1, S2, S3 of TB1 and
TB2 are connected in reverse.
2
The connection from TB1 and
TB2 to indoor controller board
CNS and CNS2 are in reverse.
1
Correct the wiring according to 7. WIRING
DIAGRAM.
TB1 — Indoor unit
TB2 — Cylinder/Hydrobox unit
2
Correct the wiring according to 7. WIRING
DIAGRAM.
TB1 — CNS
TB2 — CNS2
EF
(6607
or
6608)
Non defined check code
This code is displayed when non defined
check code is received.
1
Noise has entered transmission
wire of remote controller.
2
Noise has entered indoor/ out-
door unit connecting wire.
3
Outdoor unit is not a series of
power-inverter.
12
Turn the power off, and on again to check.
Replace indoor controller board or outdoor
controller circuit board if abnormality is
displayed again.
3
Replace outdoor unit with power-inverter type
outdoor unit.
4
Replace remote controller with MA remote
controller.