2. M-NET control
SYSTEM DESIGN
262
2-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7/ TB3 side, Booster for long M-NET wiring
1. Address should be set to Indoor units, LOSSNAY and system controller.
2. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for
transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to
2-3 "System configuration restrictions".
NOTE:
Indoor unit
MA R/C
MA R/C
(Main)
(Sub)
MA R/C
SRU
Wireless R/C
*1
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
For AG-150A, 24VDC should be used with the PAC-SC51KUA.
*3 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main"
controller and others as "sub".
Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".
*1
01
BC controller
52
BC controller
(Main)
92
02
03
30
TB15
TB5
TB02
TB5
TB5
TB2
Transmission Booster
PAC-SF46EPA
TB5
TB15
TB15
TB3
TB15
MA R/C
(Main)
(Sub)
MA R/C
TB15
Indoor unit
ME R/C
MA R/C
PZ-52SF-E
SRU
Wireless R/C
*1
*1
142
143
*2
SC*3
SC*3
41
42
43
95
45
46
TB15
TB5
TB02
TB5
LOSSNAY
TB5
TB5
TB5
TB15
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
BC controller
(Sub1)
Group 2
Group 1
Group 21
Group 32
Group 33
Group 31
Group 34
Group 35
TB7
TB7
TB7
TB3
TB2
000 or 201
203
202
Power supply unit
(PAC-SC51KUA)
51
OC
PURY
SC
TB3
91
OC
PURY
TB3
98
OC
CN41
CN40
CN41
CN40
CN41
CN40
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
PURY
3. Indoor units should be set with a branch number.
4. Assign an address to each of the sub BC controllers which equals the sum of the smallest address of the indoor units that are
connected to each sub BC controller and 50.
PZ-60
DR-E
47
TB5
TM4
LOSSNAY
Group 36