3
1. SPECIFICATIONS
OUTDOOR UNITS
Model
PUHY-RP300YJM-B(-BS)
PUHY-RP350YJM-B(-BS)
Power source
3-phase 4-wire 380-400-415V 50/60Hz
3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity
*1 kW
33.5
40.0
(Nominal)
*1 kcal / h
28,800
34,400
*1 BTU / h
114,300
136,500
Power input
kW
8.98
11.79
Current input
A
15.1-14.4-13.8
19.9-18.9-18.2
COP
kW / kW
3.73
3.39
Temp. range of
Indoor
W.B.
15.0~24.0°C(59~75°F)
15.0~24.0°C(59~75°F)
cooling
Outdoor
D.B.
-5.0~43.0°C(23~109°F)
-5.0~43.0°C(23~109°F)
Heating capacity
*2 kW
37.5
45.0
(Nominal)
*2 kcal / h
32,300
38,700
*2 BTU / h
128,000
153,500
Power input
kW
9.42
12.60
Current input
A
15.9-15.1-14.5
21.2-20.2-19.4
COP
kW / kW
3.98
3.57
Temp. range of
Indoor
D.B.
15.0~27.0°C(59~81°F)
15.0~27.0°C(59~81°F)
heating
Outdoor
W.B.
-20.0~15.5°C(-4~60°F)
-20.0~15.5°C(-4~60°F)
Indoor unit
Total capacity
50~130 % of outdoor unit capacity
50~130 % of outdoor unit capacity
connectable
Model / Quantity
P15~P250 / 1~26
P15~P250 / 1~30
Sound pressure level (measured in anechoic room) dB <A>
59
60
Refrigerant
Liquid pipe
mm (in.)
12.7(1/2) Brazed
15.88(5/8) Brazed
piping diameter
Gas pipe
mm (in.)
28.58(1-1/8) Brazed
34.93(1-3/8) Brazed
FAN
Type x Quantity
Propeller fan x 1
Propeller fan x 1
Air flow rate
m
3
/ min
185
185
L/s
3,083
3,083
cfm
6,532
6,532
Control, Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.92 x 1
0.92 x 1
*3 External static press.
0 Pa (0 mmH
2
O)
0 Pa (0 mmH
2
O)
Compressor
Type x Quantity
Inverter scroll hermetic compressor
Inverter scroll hermetic compressor
Manufacture
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Motor output
kW
8.2
9.9
Case heater
kW
0.045(240 V)
0.045(240 V)
Lubricant
MEL32
MEL32
External finish
Pre-coated galvanized steel sheets (+powder coating for -BS
type)
Pre-coated galvanized steel sheets (+powder coating for -BS
type)
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
External dimension HxWxD
mm
1,710(1,650 without legs) x 920 x 760
1,710(1,650 without legs) x 920 x 760
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/16
67-3/8(65 without legs) x 36-1/4 x 29-15/16
Protection devices
High pressure protection
High pressure sensor, High pressure switch at 4.15,3.3MPa
(601,479 psi)
High pressure sensor, High pressure switch at 4.15,3.3MPa
(601,479 psi)
Inverter circuit (COMP. / FAN)
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Compressor
Over-heat protection
Over-heat protection
Fan motor
Thermal switch
Thermal switch
Refrigerant
Type x original charge
R410A x 9.0kg (20lbs)
R410A x 9.0kg (20lbs)
Control
LEV and HIC circuit
LEV and HIC circuit
Net weight
kg (lbs)
255(563)
255(563)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
Auto-defrost mode (Reversed refrigerant cycle)
Drawing
External
KD94G725
KD94G725
Wiring
KE94C490
KE94C490
Standard attachment
Document
Installation Manual
Installation Manual
Accessory
Refrigerant conn. pipe
Refrigerant conn. pipe
Optional parts
Header: CMY-Y104/108/1010-G
Header: CMY-Y104/108/1010-G
Remarks
●
.Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
●
.Due to continuing improvement, above specifications may be subject to change without notice.
●
.Our company is unable to guarantee reliability of pre-existing pipes and pre-existing cables.
Notes :
Unit converter
1.Nominal cooling conditions (subject to JIS B8615-1)
Indoor: 27°CDB/19°CWB (81°FDB/66°FWB), Outdoor: 35°CDB (95°FDB)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-1)
Indoor: 20°CDB (68°FDB), Outdoor: 7°CDB/6°CWB (45°FDB/43°FWB)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.External static pressure option is available (30 Pa, 60 Pa/3.1 mmH
2
O, 6.1 mmH
2
O).
kcal
=kW x 860
BTU/h =kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg / 0.4536
*The specification data is
subject to rounding variation.