263
2. M-NET control
SYSTEM DESIGN
2-4-3-4. ME remote controller, Single-refrigerant-system, No system controller
1. Address should be set to Indoor units, system controller and ME remote controllers.
2. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to
2-3 "System configuration restrictions".
NOTE:
Indoor unit
ME R/C
ME R/C ME R/C
01
BC controller
52
02
03
04
05
TB5
TB02
TB5
TB5
102
ME R/C
104
105
155
TB5
TB5
ME R/C
101
Group 2
Group 1
Group 3
Group 4
TB3
51
OC
CN41
CN40
OFF
DipSW2-1
PURY
3. Indoor units should be set with a branch number.
2-4-3-5. ME remote controller, Single-refrigerant-system, System controller, LOSSNAY
1. Address should be set to Indoor units, LOSSNAY centralized controller, ME remote controllers.
2. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at
2-3 "System configuration
restrictions".
NOTE:
ME R/C ME R/C
Indoor unit
ME R/C
ME R/C
PZ-52SF-E
102
103
104
105
155
01
02
03
04
05
TB5
TB5
LOSSNAY
TB5
TB5
TB5
ME R/C
101
Group 2
Group 3
Group 1
Group 4
Group 5
201
SC
*SC can be connected to TB3 side or TB7 side;
Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
TB3
51
OC
CN41
CN40
ON
DipSW2-1
PURY
3. Indoor units should be set with a branch number.
BC controller
52
TB02
PZ-60
DR-E
06
TB5
TM4
LOSSNAY
Group 6