1. Error
Code
Overload protection
2. Error definition and error detection method
If the output current of "(Iac) >Imax (Arms)" or "THHS > TOL" is continuously detected for 10 minutes or more during inverter
operation.
3. Cause, check method and remedy
Refer to section -6- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 244)
4240
(THMU-A)
Model
Imax(Arms)
P72, P96 models
35
P120 model
53
Model
TOL
P72, P96 models
95°C [203°F]
P120 model
80°C [175°F]
Cause
Check method and remedy
(1)
Air passage blockage
Check that the heat sink cooling air passage is not blocked
(2)
Power supply environment
Power supply voltage is 188 V or above.
(3)
Inverter failure
Refer to IX [4] -6-.(page 244)
(4)
Current sensor (ACCT) failure
Refer to IX [4] -6- (4).
(5)
Compressor failure
Check that the compressor has not overheated during operation.
-> Check the refrigerant circuit (oil return section).
Refer to IX [4] -6- (2) [2].(page 246)
Содержание PUHY-P120YHMU-A
Страница 1: ......
Страница 9: ...HWE0804A GB ...
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 55: ... 46 ...
Страница 71: ... 62 ...
Страница 73: ... 64 ...
Страница 81: ... 72 ...
Страница 83: ... 74 ...
Страница 88: ... 79 HWE0804A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 82 ...
Страница 89: ... 80 ...
Страница 95: ... 86 ...
Страница 97: ... 88 ...
Страница 123: ... 114 ...
Страница 157: ... 148 ...
Страница 279: ... 270 ...
Страница 280: ... 271 HWE0804A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 273 ...
Страница 281: ... 272 ...
Страница 326: ......