[1] Functions and Factory Settings of the Dipswitches
1. Outdoor
unit
(1) Control board
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) Refer to "VII [2] Controlling the Outdoor Unit" for details.(page 96)
4) The table below shows the combination of SW2-9 and SW3-5 settings and the target evaporating temperature setting that
corresponds to each combination.
Switch
Function
Function according to switch setting
Switch setting timing
Units that re-
quire switch
setting
Note.2
OFF
ON
OFF
ON
OC
OS
SWU
1-2
Unit address setting
Set to 00 or 51-100 with the dial switch
Before power on
C
C
SW1
1-10
For self-diagnosis/
operation monitoring
Refer to the LED monitor display on the
outdoor unit board.
Anytime after power on
C
C
SW2
1
Centralized control
switch
Without connection
to the centralized
controller
With connection to
the centralized con-
troller
Before power on
B
B
2
Deletion of connec-
tion information
Normal control
Deletion
Before power on
A
-
3
Deletion of error his-
tory SW
(OC) Storage of IC/
OC error history
(OC) Deletion of IC/
OC error history
Anytime after power on
(When switched from OFF
to ON)
C
C
(OS) Storage of OS
error history
(OS) Deletion of
OS error history
4
Pump down mode
Normal control
Pump down mode
After being energized and
while the compressor is
stopped
A
-
5
-
-
-
-
-
-
6
-
-
-
-
-
-
7
Forced defrost
Note 3
Normal control
Forced defrost
starts
10 minutes
after com-
pressor
startup
Anytime af-
ter power
on (When
switched
from OFF to
ON)
A
A
8
Defrost timer setting
Note 3
50 minutes
90 minutes
Anytime after power on
(When switched from OFF
to ON)
B
B
9
Target evaporating
temperature setting
Depends on the setting combination with
the SW3-5 setting (Note 4)
Anytime after power on
A
-
10
-
-
-
-
-
-
Switch
SW2-9
OFF
ON
SW3-5
OFF
0°C [32°F]
-4°C [25°F]
ON
-2°C [28°F]
-6°C [21°F]
Содержание PUHY-P120YHMU-A
Страница 1: ......
Страница 9: ...HWE0804A GB ...
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 55: ... 46 ...
Страница 71: ... 62 ...
Страница 73: ... 64 ...
Страница 81: ... 72 ...
Страница 83: ... 74 ...
Страница 88: ... 79 HWE0804A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 82 ...
Страница 89: ... 80 ...
Страница 95: ... 86 ...
Страница 97: ... 88 ...
Страница 123: ... 114 ...
Страница 157: ... 148 ...
Страница 279: ... 270 ...
Страница 280: ... 271 HWE0804A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 273 ...
Страница 281: ... 272 ...
Страница 326: ......