VIII
Test Run Mode ]
- 140 -
HWE0804A
GB
Operation
Outdoor unit model
PUHY-P336TSHMU-A
PUHY-P96THMU-A
PUHY-
P120THMU-A
PUHY-
P120THMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor
35°C/ - [95°F/ - ]
Indoor
unit
No. of connected
units
Unit
6
No. of units in opera-
tion
6
Model
-
54/54/54/54/54/54
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe
10 [32-3/4 ]
Total pipe length
65 [213-1/4]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
37 [82]
Outdoor
unit
Electric current
A
82.2
Voltage
V
230
Compressor frequency
Hz
65
72
72
LEV open-
ing
Indoor unit
Pulse
395/395/395/395/395/395
SC (LEV1)
171
171
171
LEV2
1400
1400
1400
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
2.89/0.88
2.89/0.88
2.89/0.88
[419/128]
[419/128]
[419/128]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
74 [165] 73 [163] 73 [163]
Heat exchanger out-
let
(TH3)
46 [115] 40 [104] 40 [104]
Accumulator
inlet
10 [50] 10 [50] 10 [50]
Accumulator
outlet
10 [50] 10 [50] 10 [50]
SCC outlet (TH6)
26 [79]
20 [68]
20 [68]
Compressor
inlet
14 [57] 15 [59] 15 [59]
Compressor shell
bottom
38 [100] 42 [108] 42 [108]
Indoor
unit
LEV
inlet
25 [77] 19 [66] 19 [66]
Heat exchanger
outlet
10 [50] 10 [50] 10 [50]
Содержание PUHY-P120YHMU-A
Страница 1: ......
Страница 9: ...HWE0804A GB ...
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 55: ... 46 ...
Страница 71: ... 62 ...
Страница 73: ... 64 ...
Страница 81: ... 72 ...
Страница 83: ... 74 ...
Страница 88: ... 79 HWE0804A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 82 ...
Страница 89: ... 80 ...
Страница 95: ... 86 ...
Страница 97: ... 88 ...
Страница 123: ... 114 ...
Страница 157: ... 148 ...
Страница 279: ... 270 ...
Страница 280: ... 271 HWE0804A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 273 ...
Страница 281: ... 272 ...
Страница 326: ......