[8] Restrictions on Pipe Length
(1) End branching
P72 - P120 models
Unit: m [ft]
Operation
Pipe sections
Allowable length of
pipes
Length
Total pipe length
A+B+C+D
+a+b+c+d+e+f
1000 [3280] or less
Total pipe length (L) from the outdoor unit to the
farthest indoor unit
A+B+C+c or
A+D+f
165 [541] or less
(Equivalent length 190
[623] or less)
Total pipe length from the first branch to the far-
thest indoor unit (
)
B+C+c or
D+f
40 [131] or less
Height
difference
Between indoor and
outdoor units
Outdoor unit above in-
door unit
H
50 [164] or less
Outdoor unit below in-
door unit
H'
40 [131] or less
Between indoor units
h
15 [49] or less
L
B
e
h
f
6
1
a
c
b
3
2
5
A
D
C
d
4
H
H
'
Branch joint
Indoor Indoor
Indoor
Indoor Indoor Indoor
cap
Branch header
(Outdoor unit above indoor unit)
(Outdoor unit below indoor unit)
Outdoor unit
First branch
(Branch joint)
Содержание PUHY-P120YHMU-A
Страница 1: ......
Страница 9: ...HWE0804A GB ...
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 55: ... 46 ...
Страница 71: ... 62 ...
Страница 73: ... 64 ...
Страница 81: ... 72 ...
Страница 83: ... 74 ...
Страница 88: ... 79 HWE0804A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 81 2 Principal Parts and Functions 82 ...
Страница 89: ... 80 ...
Страница 95: ... 86 ...
Страница 97: ... 88 ...
Страница 123: ... 114 ...
Страница 157: ... 148 ...
Страница 279: ... 270 ...
Страница 280: ... 271 HWE0804A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 273 ...
Страница 281: ... 272 ...
Страница 326: ......