INSTALLATION
All series of air conditioners are designed for outdoor installations and are to be placed on a slab or rooftop, however if
the air conditioner is to be installed in a plant room application, please contact your equipment supplier prior to
installation.
1. Basic space required
A space of at least 250 mm is necessary at the back for inlet air. Taking
servicing, etc. from the rear into account, a space of about 450 mm should
be provided, the same as at the front.
2. When there is an obstruction above the unit
3. When unit is surrounded by walls
Note:
• Wall heights (H) of the front and the back sides shall be within
overall height of unit.
• If the panel height is exceeded, add the “h” dimension to L
1
and
L
2
.
L
1
: 450 L
2
: 250
Example:
When h is 100,
the
L
1
dimension becomes 450 + 100 = 550 mm.
4. Continuous installation
• Space required for collective installation and continuous installation:
When installing several units, leave the space between each unit
considering passage for air and people.
• Open in the two directions.
• In case wall height (H) exceeds overall height of unit, add “h” dimension
(h = wall height <H> – overall height of unit) to * marked dimension.
[1] Space required around units
<B>
2.
300
45
<A>
250
450
1.
650
325
A
H
h
Hh
L
1
=
>
L
2
=
>
<A>
<B>
3.
L1
A
L2
4.
<A> Top view
<B> Side view
A
Front
B
Must be open
C
Wall height (H)
L
1
: 450
L
2
: 250
250
450
450
A
A
A
C
B
B
*
• Models PRH-P8MYA/P10MYA