Communication de-
mand capacity
0 - 255
Abnormal thermistor
display
1 - 3, –
Outdoor-side fan
output at abnormal
stop
0 - 100
LEV opening angle (/5)
at abnormal stop
0 - 400
Outdoor-side
condenser/evaporater
temperature
at abnormal stop
–39 - 88
Discharge super heat
(SHd) at abnormal stop
0 - 216
Cooling:
Heating:
Sub cool (Sc) at
abnormal stop
0 - 130
Cooling:
Heating:
0 - 255
When communication demand not set: 100%
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
<Example> When 100,
every other second
1
←→
100
1 - 3, –
1: Outdoor-side liquid temp thermistor (TH1)
2: Outdoor-side discharge temp thermistor (TH2)
3: Outdoor-side condenser/evaporater temp thermistor
(TH3)
–: No abnormal thermistor
0 - 100
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
<Example> When 100,
every other second
–
←→
00
0 - 400
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
<Example> When 200,
every other second
2
←→
00
–39 - 88
(When 0
°
C or lower, “–”and temperature are displayed
alternately.)
<Example> When –10,
every other second
–
←→
–10
0 - 216
(When 100
°
C or higher, 100s digit and 10s and units
digits are displayed alternately.)
<Example> When 150,
every other second
–
←→
50
0 - 130
(When 100
°
C or higher, 100s digit and 10s and units
digits are displayed alternately.)
<Example> When 100,
every other second
1
←→
00
%
–
%
5 pulses
°
C
°
C
°
C
SW2 setting
Display contents
Description of display
Unit
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
Outdoor-side
TH2
– Outdoor-side
TH3
Outdoor-side
TH2
– Indoor-side
TH6
Outdoor-side
TH3
– Outdoor-side
TH1
Indoor-side
TH6
– Indoor-side
TH5
- 51 -