Start
Piping work complete?
Check that mains power is OFF
Turn on emergency operation switch
(SWE) on indoor-side controller board
Short CN31 (emergency operation
connector) on outdoor-side controller board
Check that emergency operation starts,
and that operation mode display flashes
Set operation mode (cooling or heating) with SW4-2 on outdoor-side
board (SW4-1 not used)
SW4
Cooling
Heating
OFF ON
1
2
NO
YES
4) Emergency operation method
* Before starting, recheck that the trouble allows
emergency operation.
5)
Emergency operation release method
Turn off mains power.
a)
Turn on mains power
e)
Turn off emergency operation switch
(SWE) on indoor-side controller board
b)
Open CN31 (emergency operation
connector) on outdoor-side controller board
c)
SW4
OFF ON
1
2
Set SW4-2 as shown below
d)
Turn on mains power
✻
1: For each refrigerant circuit
- 59 -