[5] Simple parts check method
• PRH-P8MYA/P10MYA/P16MYA/P20MYA
Part name
Thermistor (TH1)
<Outdoor-side liquid
temperature detection>
Thermistor (TH4)
<Indoor-side intake
temperature>
Thermistor (TH5)
<Indoor-side unit piping
temperature>
Thermistor (TH6)
<Indoor-side unit condenser/
evaporater temperature>
Thermistor (TH2)
<Discharge temperature
detection>
Thermistor (TH3)
<Outdoor-side condenser/
evaporater
temperature
detection>
Outdoor-side fan motor
Compressor
Thermal protector
trip temperature
135
±
5˚C : ON
88
±
5˚C : OFF
Judgment instructions
Disconnect the connector and measure the resistance value with a multimeter.
(Ambient temperature 10 ˚C to 30 ˚C)
Measure the resistance value across the terminals with a multimeter. (Winding
temperature 20 ˚C)
Measure the resistance value across the terminals with a multimeter. (Winding
temperature 20 ˚C)
Normal
4.3 k
Ω
~9.6 k
Ω
160 k
Ω
~410 k
Ω
Abnormal
Open or short
(Based on thermistor characteristic table (next page))
TH1, 3, 4, 5, 6
TH2
White
Blue
Black
Normal
45.5
Ω
Abnormal
Open or short
Motor lead wire
Between 2 phases
Normal
PRH-P8, 16MYA
Each phase 1.574
Ω
PRH-P10, 20MYA
Each phase 1.263
Ω
Abnormal
Open or short
Open or short
Red
Indoor-side fan motor
Measure the resistance value across the terminals with a multimeter. (Winding
temperature 20 ˚C)
White
Black
Red
Normal
13.2
Ω
10.2
Ω
6.4
Ω
3.4
Ω
PRH-P8MYA PRH-P10MYA PRH-P16MYA PRH-P20MYA
Motor lead wire
Between 2 phases
Open or short
Abnormal
PRH-P8, 10, 16, 20MYA
Motor lead wire
Between 2 phases
- 53 -