- 50 -
(2) System with MA remote controller and AG-150A
1) System with multiple indoor units (10HP, 20HP)
Control Wiring Diagram
Notes
Maximum Allowable Length
1. Be sure to use odd numbers to set the address for indoor units
(10 HP and 20HP connected to the one outdoor unit).
2. To set the indoor unit address for 20 HP connected to two outdoor units, use odd
numbers for the top controllers and use even numbers for the bottom controllers (Main
controller plus 1).
3. Use the power supply switch connector (CN41) on the outdoor unit as is.
4. It is not necessary to ground the S terminal of transmission line terminal board for
centralized controller on the outdoor unit.
5 No more than two main/sub remote controllers can be connected to the indoor unit in the
same group. When more than two remote controllers are present in the system,
disconnect MA remote controller from TB15 in the indoor unit.
6. Put both types of the addresses for P500-type indoor units in the same group when
setting groups for indoor units with system controller (ex. AG-150A).
<a. Indoor/Outdoor transmission line>
L1, L2, L3 200m
<b. Transmission Line for Centralized Control>
L33 + L32 + L31 + L34 + L3 500m
L1 + L31 + L34 + L3 500m
<c. MA Remote Controller Line>
Total Length (0.3 - 1.25mm
2
)
m1 200m
Wiring and Address Setting
<a. Indoor/Outdoor transmission line>
Same as (1) 1).
<b. Transmission line for centralized control>
Daisy-chain terminals M1 and M2 on the terminal block for transmission line for centralized control (TB7) on each outdoor unit (OC).
*Only use shielded cables.
[Shielded cable connection]
To ground the shielded cable, daisy-chain the S-terminals on the terminal block (TB7) on each of the outdoor units.
<c. Switch setting>
Address setting is required as follows.
MA
TB15
1
2
A
B
OC
TB3
TB7
M1
M1 M2 S
53
IC
MA
TB5-1
A1 B1 S
03
TB5-2
A2 B2 S
TB15
1
2
A
B
04
OC
TB3
TB7
M1M2
M1M2 S
54
OC
TB3
TB7
M1M2
M2
M1M2S
51
IC
TB5-1
A1 B1S
01
L1
Use CN41 as is.
Power
Supply
A B S
AG-150A
A B S
L32
L33
Option
DC power supply line
(DC24V)
L34
m1
L2
L3
m1
Use CN41 as is.
Use CN41 as is.
* There is one indoor controller
board inside indoor unit.
* There are two indoor controller
boards inside indoor unit.
L31
not connect
not connect
Main Controller
Sub Controller
Settings to be made with the sub/main switch
IC
IC
OC
1
2
Notes
3
MA
MA
51~100
02~50
01~49
00
00
Setting not required.
Sub Controller
Steps
Unit or controller
Main
(10HP, 20HP)
Sub
(20HP)
Indoor
unit
MA
remote
controller
Address
setting range
Address setting method
Outdoor unit
Factory
setting
Main
Assign a sequential odd number starting with
"01" to the upper indoor controller.
Add 50 to the address assigned to the indoor unit
connected to the system with one outdoor unit.
Assign sequential numbers starting with the
address of the main unit in the same group.
(Main unit a1)