- 29 -
(3) PFD-P500VM-E (single refrigerant circuit system)
IU
Outdoor Twinning Kit
CMY-Y100VBK2
Note1. If the A/C system is designed to use cooling mode under outdoor temperature 10°C, H’<=15m.
Note2. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m)=Actual piping "M" x Quantity of bent.
H (OU above IU)
H' (OU under IU)
h
T
A
L
S
IU: Indoor unit, OU: Outdoor unit
Fig.IV-1-(3)A: Piping scheme
2m
To indoor unit
To indoor unit
To indoor unit
2m
To indoor unit
Trap (gas
pipe only)
Upward
incline
Downward
incline
Install the pipes from the outdoor unit to the branch
joint with a downward incline.
If the length of pipe between the branch joint and outdoor
unit exceeds 2 m, provide at rap at a distance 2 m or less
from the branch joint.
OK
NG
OU
OU
max
Table: I V- 1 - ( 3 ) - 2 . Bent equivalent length "M"
M (m/bent)
Outdoor Model
PUHY-P500
0.50
Table: I V- 1 - ( 3 ) - 1 . Piping length
(m)
Max. length
Piping in the figure
Item
Max. equivalent length
A
Height between OU and IU (OU above IU)
Height between OU and IU (OU above IU)
OU: Outdoor Unit, IU: Indoor Unit
190
Farthest IU from OU (L)
h
-
Height between OU and OU
S+T
-
Distance between OU and OU
H
H'
-
-
(mm)
Outdoor
CMY-Y100VBK2
CMY-Y100VBK2; PUHY-P500
Table: I V- 1 - ( 3 ) - 3 . Piping "A" size selection rule
(mm)
Indoor Unit size
P500
Table: I V- 1 - ( 3 ) - 4 . Indoor unit piping size selection rule
165
0.1
10
50
40
Pipe(Gas)
Pipe(Liquid)
ø28.58
ø15.88
Pipe(Gas)
Pipe(Liquid)
ø28.58
ø15.88