(2) Part Load Performance
PFD unit +PUHY-P250YJM-A, PUHY-P500YSJM-A
PFD unit +PQHY-P250YHM-A
10HP System
Indoor Unit
: PFD-P250VM-E
Outdoor Unit
: PUHY-P250YJM-A
Cooling
Capacity (kW)
100%
Capacity
90%
Capacity
80%
Capacity
70%
Capacity
60%
Capacity
50%
Capacity
40%
Capacity
40 °C
26.5
9.83
8.67
7.70
6.89
6.20
5.60
5.34
35 °C
28.0
9.30
8.18
7.27
6.51
5.86
5.24
4.89
30 °C
29.3
8.76
7.71
6.85
6.13
5.53
4.87
4.58
25 °C
30.5
8.23
7.24
6.44
5.73
5.21
4.69
4.47
20 °C
31.5
7.70
6.78
6.07
5.52
5.03
4.63
4.45
15 °C
32.4
7.44
6.65
6.01
5.47
5.00
4.60
4.43
* Indoor air temperature condition: 27°CDB/19°CWB
20HP System
Indoor Unit
: PFD-P500VM-E
Outdoor Unit
: PUHY-P250YJM-A × 2, PUHY-P500YSJM-A
Cooling
Capacity (kW)
100%
Capacity
90%
Capacity
80%
Capacity
70%
Capacity
60%
Capacity
50%
Capacity
40%
Capacity
30%
Capacity
40 °C
53.0
19.66
17.34
15.40
13.79
12.41
11.20
10.19
9.13
35 °C
56.0
18.60
16.37
14.55
13.02
11.72
10.48
9.29
8.20
30 °C
58.6
17.53
15.43
13.70
12.27
11.06
9.74
8.61
7.63
25 °C
61.0
16.47
14.49
12.89
11.46
10.25
9.30
8.42
7.56
20 °C
63.1
15.41
13.57
12.14
11.05
10.06
9.26
8.36
7.51
15 °C
64.9
14.88
13.31
12.02
10.95
10.01
9.21
8.32
7.47
* Indoor air temperature condition: 27°CDB/19°CWB
Outdoor unit inlet
temp. (°CDB)
System Power input (kW)
Outdoor unit inlet
temp. (°CDB)
System Power input (kW)
10HP System
Indoor Unit
: PFD-P250VM-E
Heat source Unit : PQHY-P250YHM-A
* Indoor air temperature condition: 27°CDB/19°CWB
20HP System
Indoor Unit
: PFD-P500VM-E
Heat source Unit : PQHY-P250YHM-A × 2
* Indoor air temperature condition: 27°CDB/19°CWB
25.4
9.00 8.02 7.24 6.59 6.08 5.71
26.7
8.50 7.59 6.87 6.28 5.80 5.46
28.0
7.95 7.13 6.47 5.93 5.50 5.20
28.0
7.37 6.64 6.05 5.57 5.19 4.91
28.0
6.95 6.28 5.75 5.31 4.95 4.70
28.0
6.69 6.06 5.55 5.14 4.81 4.57
50.8
17.99 16.04 14.47 13.19 12.16 11.43 9.74 8.58
53.4
16.99 15.19 13.74 12.55 11.61 10.93 9.37 8.30
56.0
15.90 14.26 12.95 11.87 11.01 10.39 8.97 8.00
56.0
14.74 13.28 12.10 11.14 10.37 9.82 8.55 7.69
56.0
13.91 12.57 11.49 10.61 9.91 9.40 8.25 7.45
56.0
13.37 12.11 11.10 10.27 9.61 9.14 8.35 7.31
Cooling
Capacity (kW)
100%
Capacity
90%
Capacity
80%
Capacity
70%
Capacity
60%
Capacity
50%
Capacity
40 °C
35 °C
30 °C
25 °C
20 °C
15 °C
Cooling
Capacity (kW)
100%
Capacity
90%
Capacity
80%
Capacity
70%
Capacity
60%
Capacity
50%
Capacity
40%
Capacity
30%
Capacity
40 °C
35 °C
30 °C
25 °C
20 °C
15 °C
Outdoor unit inlet
temp. (°CDB)
System Power input (kW)
Outdoor unit inlet
temp. (°CDB)
System Power input (kW)