![Mitsubishi Electric PQHY-P250YHM-A Скачать руководство пользователя страница 52](http://html.mh-extra.com/html/mitsubishi-electric/pqhy-p250yhm-a/pqhy-p250yhm-a_data-book_1811134052.webp)
- 43 -
4. Control Wiring
Restrictions when the PFD-type indoor units are connected (related to the system)
The PFD-type indoor units cannot be connected to the ME remote controller.
The address settings must be made on this system.
The following functions cannot be selected on the PFD-type indoor units.
a) Switching between automatic power recovery Enabled/Disabled (Fixed to "Enabled" in the PFD-type indoor units)
b) Switching between power source start/stop (Fixed to "Disabled" in the PFD-type indoor units)
The PFD-type indoor units and other types of indoor units cannot be grouped.
The following functions are limited when the system controller (such as G-50A) is connected.
a) To perform group operation in the system with two refrigerant circuits (combination of two outdoor units and one indoor
unit: P500 model only), the addresses of the controller boards No.1 and No.2 on a indoor unit must be set within a group.
b) The local operation cannot be prohibited with the system controller.
c) When the switches of the PFD-type indoor units are set as follows, the unit ON/OFF operation cannot be made with the
system controller.
· When the SW9 (Normal/Local) is set to "Local"
· When the DipSW1-10 on the control circuit board is set to "ON"
d) The PFD type indoor units cannot be grouped with other types of indoor units.
(1) Specifications of control wiring and maximum length of wiring
Control cables are categorized into two types: transmission cable and remote controller cable. Use the appropriate type of
cables, and observe the maximum allowable length specified for a given system configuration.
When the source of noise is located adjacent to the unit, the use of shield cable as well as moving the unit as far away from
the noise source are recommended.
1) Transmission line (M-NET transmission line)
2) Remote control wiring
*1: Cables with a diameter of 0.75mm
2
or smaller recommended for easier handling.
System component
For multiple-refrigerant system
Wiring specifications
Facility type
(noise level measurement)
All types of facilities
Cable type
Shield cable
CVVS · CPEVS · MVVS
No. of cable
2-core cable
Diameter
Over 1.25mm
2
Maximum indoor-outdoor transmission cable length
Maximum 200 m
Maximum length of transmission line for centralized
control and indoor-outdoor transmission cables
(Maximum cable distance via outdoor unit)
Maximum 500 m
The maximum cable distance from the power supply unit on the
centralized controller transmission line to each outdoor unit or to
the system controller is 200 meters.
MA remote controller
Wiring specifications
Cable type
VCTF · VCTFK · CVV · CVS · VVR · VVF · VCT
No. of cable
2-core cable
Diameter
0.3~1.25mm
2
*1
Total length
Maximum length: 200 m