6
9
9.2
PQHY-P·T(S)LMU-A/Y(S)LMU-A
A
(Unit: mm [in])
Heat source model
Unit combination
A
A1
*3
A2
*3
Unit1
Unit2
Liquid Side
Gas Side
Liquid Side
Gas Side
Liquid Side
Gas Side
P72T/YLMU
-
-
ø9.52[3/8]
ø19.05[3/4]
-
-
-
-
P96T/YLMU
-
-
*1
ø9.52[3/8]
ø22.2[7/8]
-
-
-
-
P120T/YLMU
-
-
*2
ø9.52[3/8]
ø22.2[7/8]
-
-
-
-
P144T/YLMU
-
-
ø12.7[1/2]
ø28.58[1-1/8]
-
-
-
-
P144T/YSLMU
P72
P72
ø12.7[1/2]
ø28.58[1-1/8]
ø9.52[3/8]
ø19.05[3/4]
ø9.52[3/8]
ø19.05[3/4]
P168T/YLMU
-
-
ø15.88[5/8]
ø28.58[1-1/8]
-
-
-
-
P168T/YSLMU
P96
P72
ø15.88[5/8]
ø28.58[1-1/8]
ø9.52[3/8]
ø22.2[7/8]
ø9.52[3/8]
ø22.2[7/8]
P192T/YLMU
-
-
ø15.88[5/8]
ø28.58[1-1/8]
-
-
-
-
P192T/YSLMU
P96
P96
ø15.88[5/8]
ø28.58[1-1/8]
ø9.52[3/8]
ø22.2[7/8]
ø9.52[3/8]
ø22.2[7/8]
P216T/YLMU
-
-
ø15.88[5/8]
ø28.58[1-1/8]
-
-
-
-
P216T/YSLMU
P120
P96
ø15.88[5/8]
ø28.58[1-1/8]
ø12.7[1/2]
ø22.2[7/8]
ø12.7[1/2]
ø22.2[7/8]
P240T/YLMU
-
-
ø15.88[5/8]
ø28.58[1-1/8]
-
-
-
-
P240T/YSLMU
P120
P120
ø15.88[5/8]
ø28.58[1-1/8]
ø12.7[1/2]
ø28.58[1-1/8]
ø12.7[1/2]
ø28.58[1-1/8]
P288T/YSLMU
P144
P144
ø19.05[3/4]
ø34.93[1-3/8]
ø12.7[1/2]
ø28.58[1-1/8]
ø12.7[1/2]
ø28.58[1-1/8]
P312T/YSLMU
P168
P144
ø19.05[3/4]
ø34.93[1-3/8]
ø15.88[5/8]
ø28.58[1-1/8]
ø12.7[1/2]
ø28.58[1-1/8]
P336T/YSLMU
P168
P168
ø19.05[3/4]
ø41.28[1-5/8]
ø15.88[5/8]
ø28.58[1-1/8]
ø15.88[5/8]
ø28.58[1-1/8]
P360T/YSLMU
P192
P168
ø19.05[3/4]
ø41.28[1-5/8]
ø15.88[5/8]
ø28.58[1-1/8]
ø15.88[5/8]
ø28.58[1-1/8]
PQRY-P·T(S)LMU-A/Y(S)LMU-A
A
(Unit: mm [in])
Heat source model
Unit combination
A
A1
*3
A2
*3
Unit1
Unit2
High press.
Side
Low press.
Side
High press.
Side
Low press.
Side
High press.
Side
Low press.
Side
P72T/YLMU
-
-
ø15.88[5/8]
ø19.05[3/4]
-
-
-
-
P96T/YLMU
-
-
ø19.05[3/4]
ø22.2[7/8]
-
-
-
-
P120T/YLMU
-
-
ø19.05[3/4]
ø22.2[7/8]
-
-
-
-
P144T/YLMU
-
-
ø22.2[7/8]
ø28.58[1-1/8]
-
-
-
-
P144T/YSLMU
P72
P72
ø22.2[7/8]
ø28.58[1-1/8]
ø15.88[5/8]
ø19.05[3/4]
ø15.88[5/8]
ø19.05[3/4]
P168T/YLMU
-
-
ø22.2[7/8]
ø28.58[1-1/8]
-
-
-
-
P168T/YSLMU
P96
P72
ø22.2[7/8]
ø28.58[1-1/8]
ø19.05[3/4]
ø22.2[7/8]
ø15.88[5/8]
ø19.05[3/4]
P192T/YLMU
-
-
ø22.2[7/8]
ø28.58[1-1/8]
-
-
-
-
P192T/YSLMU
P96
P96
ø22.2[7/8]
ø28.58[1-1/8]
ø19.05[3/4]
ø22.2[7/8]
ø19.05[3/4]
ø22.2[7/8]
P216T/YLMU
-
-
ø28.58[1-1/8]
ø28.58[1-1/8]
-
-
-
-
P216T/YSLMU
P120
P96
ø28.58[1-1/8]
ø28.58[1-1/8]
ø19.05[3/4]
ø22.2[7/8]
ø19.05[3/4]
ø22.2[7/8]
P240T/YLMU
-
-
ø28.58[1-1/8]
ø34.93[1-3/8]
-
-
-
-
P240T/YSLMU
P120
P120
ø28.58[1-1/8]
ø34.93[1-3/8]
ø19.05[3/4]
ø22.2[7/8]
ø19.05[3/4]
ø22.2[7/8]
P288T/YSLMU
P144
P144
ø28.58[1-1/8]
ø34.93[1-3/8]
ø22.2[7/8]
ø28.58[1-1/8]
ø22.2[7/8]
ø28.58[1-1/8]
P312T/YSLMU
P168
P144
ø28.58[1-1/8]
ø34.93[1-3/8]
ø22.2[7/8]
ø28.58[1-1/8]
ø22.2[7/8]
ø28.58[1-1/8]
P336T/YSLMU
P168
P168
ø28.58[1-1/8]
ø41.28[1-5/8]
ø22.2[7/8]
ø28.58[1-1/8]
ø22.2[7/8]
ø28.58[1-1/8]
*1 ø12.7 [1/2] for over 90m
*2 ø12.7 [1/2] for over 40m
*3 The pipe sizes listed in columns A1 to A3 in this table correspond to the sizes for the models listed in the unit 1, 2, and 3 columns. When the order of the models
for unit 1, 2, and 3 change, make sure to use the appropriate pipe size.
*4
B
If the piping length after the first joint exceeds 40 m (≤ 90 m), use the one size larger liquid pipe for the indoor unit. (for PQHY-P·T(S)LMU-A/Y(S)LMU-A)
*5
C
When the height difference between the indoor units is 15 m or greater (≤ 30 m), use the one size larger liquid pipe for the indoor unit (lower side).
(for PQHY-P·T(S)LMU-A/Y(S)LMU-A)