33
GB
<Maximum Lengths>
1
ME Remote controller [Fig. 11.3.1] [Fig. 11.3.4] (P.15, 16)
•
Max length via heat source units: L
1
+L
2
+L
3
+L
4
and L
1
+L
2
+L
3
+L
5
and L
1
+L
2
+L
6
500 m [1,640 ft] (1.25 mm
2
[AWG 16] or more)
•
Max transmission cable length: L
1
and L
3
+L
4
and L
3
+L
5
and L
6
and L
2
+L
6
200 m [656 ft] (1.25 mm
2
[AWG 16] or more)
•
Remote controller cable length:
1
,
2
,
3
,
4
10 m [32 ft] (0.3 to 1.25 mm
2
[AWG 22 to 16])
If the length exceeds 10 m [32 ft], use a 1.25 mm
2
[AWG 16] shielded wire. The length of this section (L
8
) should be included in the
calculation of the maximum length and overall length.
2
MA Remote controller [Fig. 11.3.2] [Fig. 11.3.5] (P.15, 17)
• Max length via heat source unit (ME cable): L
1
+L
2
+L
3
+L
4
and L
1
+L
2
+L
6
500 m [1,640 ft] (1.25 mm
2
[AWG 16] or more)
• Max transmission cable length (ME cable): L
1
and L
3
+L
4
and L
6
and L
2
+L
6
200 m [656 ft] (1.25 mm
2
[AWG 16] or more)
•
Remote controller cable length:
m
1
+
m
2
and
m
1
+
m
2
+
m
3
+
m
4
200 m [656 ft] (0.3 to 1.25 mm
2
[AWG 22 to 16])
3
Transmission booster [Fig. 11.3.3] [Fig. 11.3.6] (P.16, 17)
• Max transmission cable length (ME cable):
For PQHY
1
L
11
+ L
12
+ L
13
+ L
15
+ L
16
200 m [656 ft] (1.25 mm
2
[AWG 16])
2
L
11
+ L
12
+ L
13
+ L
15
+ L
17
200 m [656 ft] (1.25 mm
2
[AWG 16])
3
L
11
+ L
12
+ L
14
200 m [656 ft] (1.25 mm
2
[AWG 16])
4
L
16
+ L
15
+ L
13
+ L
14
, L
14
+ L
13
+ L
15
+ L
17
200 m [656 ft] (1.25 mm
2
[AWG 16])
For PQRY
1
L
11
+ L
12
+ L
13
+ L
14
+ L
16
+ L
17
200 m [656 ft] (1.25 mm
2
[AWG 16])
2
L
11
+ L
12
+ L
13
+ L
14
+ L
16
+ L
18
200 m [656 ft] (1.25 mm
2
[AWG 16])
3
L
11
+ L
12
+ L
13
+ L
15
200 m [656 ft] (1.25 mm
2
[AWG 16])
4
L
17
+ L
16
+ L
14
+ L
15
, L
15
+ L
14
+ L
16
+ L
18
200 m [656 ft] (1.25 mm
2
[AWG 16])
•
Remote controller cable length:
1
,
2
10 m [32 ft] (0.3 to 1.25 mm
2
[AWG 22 to 16])
If the length exceeds 10 m [32 ft], use 1.25 mm
2
[AWG 16] shielded cable and calculate the length of that portion (L
15
and L
18
) as
within the total extended length and the longest remote length.
11.4. Wiring of main power supply and equipment capacity
Schematic Drawing of Wiring (Example)
[Fig. 11.4.1] (P.17)
A
Switch (Breakers for wiring and current leakage)
B
Breakers for current leakage
C
Heat source unit
D
Pull box
E
Indoor unit
F
BC controller (standard or main) (for PQRY-P·T(S)LMU-A/Y(S)LMU-A)
F
'
BC controller (sub) (for PQRY-P·T(S)LMU-A/Y(S)LMU-A)
Thickness of wire for main power supply, capacities of the switch and system impedance
Model
Minimum wire thickness
(mm
2
[AWG])
Switch (A)
Breaker
for wiring
(NFB) (A)
Breaker for current leakage
Maximum
Current
(A)
Main cable
Ground
Capacity
Fuse
WY
PQHY-P72TLMU-A/YLMU-A
3.3[12]/2.1[14]
3.3[12]/2.1[14]
20/15
20/15
20/15
20A/15A 30mA or 100mA 0.1sec, or less
15.3/6.9
PQHY-P96TLMU-A/YLMU-A
5.3[10]/2.1[14]
5.3[10]/2.1[14]
25/15
25/15
25/15
25A/15A 30mA or 100mA 0.1sec, or less
22.1/9.9
PQHY-P120TLMU-A/YLMU-A
8.4[8]/3.3[12]
8.4[8]/3.3[12]
40/20
40/20
40/20
40A 100mA/20A 30mA or 100mA 0.1sec, or less
33.9/15.3
PQHY-P144TLMU-A/YLMU-A
13.3[6]/3.3[12]
13.3[6]/3.3[12]
50/20
50/20
50/20
50A 100mA/20A 30mA or 100mA 0.1sec, or less
41.4/18.8
PQHY-P168TLMU-A/YLMU-A
13.3[6]/5.3[10]
13.3[6]/5.3[10]
60/25
60/25
60/25
60A 100mA/25A 30mA or 100mA 0.1sec, or less
51.8/23.4
PQHY-P192TLMU-A/YLMU-A
21.2[4]/5.3[10]
21.2[4]/5.3[10]
70/30
70/30
70/30
70A 100mA/30A 30mA or 100mA 0.1sec, or less
64.5/29.1
PQHY-P216TLMU-A/YLMU-A
33.6[2]/8.4[8]
33.6[2]/8.4[8]
90/40
90/40
90/40
90A/40A 100mA 0.1sec, or less
82.5/37.2
PQHY-P240TLMU-A/YLMU-A
33.6[2]/13.3[6]
33.6[2]/13.3[6]
100/50
100/50
100/50
100A/50A 100mA 0.1sec, or less
93.8/42.3
WR2
PQRY-P72TLMU-A/YLMU-A
3.3[12]/2.1[14]
3.3[12]/2.1[14]
20/15
20/15
20/15
20A/15A 30mA or 100mA 0.1sec, or less
15.3/6.9
PQRY-P96TLMU-A/YLMU-A
5.3[10]/2.1[14]
5.3[10]/2.1[14]
25/15
25/15
25/15
25A/15A 30mA or 100mA 0.1sec, or less
22.1/9.9
PQRY-P120TLMU-A/YLMU-A
8.4[8]/3.3[12]
8.4[8]/3.3[12]
40/20
40/20
40/20
40A 100mA/20A 30mA or 100mA 0.1sec, or less
33.9/15.3
PQRY-P144TLMU-A/YLMU-A
13.3[6]/3.3[12]
13.3[6]/3.3[12]
50/20
50/20
50/20
50A 100mA/20A 30mA or 100mA 0.1sec, or less
41.4/18.8
PQRY-P168TLMU-A/YLMU-A
13.3[6]/5.3[10]
13.3[6]/5.3[10]
60/25
60/25
60/25
60A 100mA/25A 30mA or 100mA 0.1sec, or less
51.8/23.4
PQRY-P192TLMU-A/YLMU-A
21.2[4]/5.3[10]
21.2[4]/5.3[10]
70/30
70/30
70/30
70A 100mA/30A 30mA or 100mA 0.1sec, or less
64.5/29.1
PQRY-P216TLMU-A/YLMU-A
33.6[2]/8.4[8]
33.6[2]/8.4[8]
90/40
90/40
90/40
90A/40A 100mA 0.1sec, or less
82.5/37.2
PQRY-P240TLMU-A/YLMU-A
33.6[2]/13.3[6]
33.6[2]/13.3[6]
100/50
100/50
100/50
100A/50A 100mA 0.1sec, or less
93.8/42.3
1. Use dedicated power supplies for the heat source unit and indoor unit. Ensure OC and OS are wired individually.
2. Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter.
Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the CSA22-1 and ANSI/NFPA No.70.
5. Power supply cords of parts of appliances for heat source use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57).
6. A switch with at least 3 mm [1/8in] contact separation in each pole shall be provided by the Air Conditioner installer.
Warning:
• Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections. If connections are not fixed firmly,
heating or fire may result.
•
Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
Caution:
•
Some installation sites may require attachment of an earth leakage breaker for the inverter. If no earth leakage breaker is installed, there is a danger of
electric shock.
• Do not use anything other than a breaker and fuse with the correct capacity. Using a fuse or wire of too large capacity may cause malfunction or fire.