7
Given below are an explanation of the layout of the Table Setting Tool main window and an explanation on
how to use the various utilities available from the menu bar.
Outline of Table Settings
●
STEP 1 (Setting the number of G-50A units to be connected. “SET.CSV” file will be created.)
The PLC software for general equipment control can send interlock commands to up to 2 G-50A units.
On the “SET.CSV” screen, the number of G-50A units to be connected will be selected. The default setting is 0.
Table 4-1 Setting the number of G-50A to be controlled
No. of G-50A connected
Settings on the Table Setting Tool
Remarks
No interlock control
commands issued
No table settings required
(0:0set)
-
Interlock control
commands to one G-50A
unit
1: 1 set
When general equipment is controlled on
the basis of general equipment operating
condition input, G-50A is irrelevant.
In this case, set it to 1.
Interlock control
commands to 2 G-50A
units
2: 2 sets
-
●
STEP 2 (Setting the operating output format for the general equipment. “PARA.CSV” file will be created.)
On the “PRAR.CSV” screen, operating output format is set for the PLC software for general equipment to control
the general equipment. Three types of settings are possible. To change the operating output format for the
general equipment, this setting is required even when interlock control is not used.
Default setting is A-contact pulse. Pulse width is 1sec.
Pattern 1 (A-contact pulse *sec)
*sec: pulse width
Pattern 2 (B-contact pulse *sec)
*sec: pulse width
Patter 3 (level)
*The pulse width can be set to any arbitrary value in 0.1 sec increments.
Table 4-2 Setting the signal output format
Type of Control
Settings on the Table Setting Tool
Remarks
No interlock control
No table settings required
-
Interlock control
A-contact pulse 1 sec
No settings required
Check the settings for operating output format.
-
Interlock control
A-contact pulse setting
other than 1 sec
Make the settings for operating output format.
This setting can be made for each piece of
equipment.
-
●
STEP 3 (Interlock settings. “TABLE.BIN” file will be created.)
On the “TABLE.BIN” screen, interlock settings are made in the following order. Interlock control is not selected
as a default.
1). Set the type and number of input sources (trigger). (Choose from among the available options on the screen.)
2). Set the type and number of output sources. (Choose from among the available options on the screen.)
3). Make the interlock setting. (Link the input source and output source that are set in steps 1) and 2) above.)
In step 3) above, up to 50 output contents can be set for each input source. (Example: Card key 1 (General
equipment 1) is turned on
→
Group 1 indoor units OFF-----Group 50 indoor units OFF)
4. Screen Configuration and Various Utilities