15 

5-4-2    Selecting the output source 

On the [Selection of output source] screen representing the wizard screen for table file setting, select the 
object to be used for the output source. On this screen, in order to use it for the input/output relations, output 
source candidate is set up. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

     

Figure 5-5. Setting screen to select output source 

 
 
 

(1) Enter the desired number of output sources. 

*The default value is set to [0]. Set it by the 

   

  button operation or numerical input. 

 

(2) Select the objective output source from the classification 1, 2 and output source columns.   

* In the columns of classification 1 and 2, the selection in addition to [All] is required. Further, the object of the same output  
source can not be selected. 

 

(3) After finishing the setting, click the [Next] button. The next setting screen is displayed. 

*Clicking the [Cancel] button returns to the initial setting screen without saving the set detail. Clicking the [Back] button returns to the 
former setting screen.   

 
 
 
 
 
 
 
 
 
 

[Next] button 

For advancing to the next setting 

  screen 

 

[Cancel] button 

For returning to initial setting     

    screen without saving set detail 

(1)Setting the output 
 source number 

First, the number of objective 
output sources are set. Can be 
set up to 10,000 maximum. 

(2)Selecting the output 
source 

The output source objects are     

    selected from the classification 
    1, 2 and output source columns.

 

[Back] button 

For returning to the former setting 

  screen. 

 

Request 

z

 

In selecting the input source, you are kindly requested to select the object actually to be used.

 
Notice 

z

 

The objects of output source; 

ON/OFF of air conditioner group (including Ventilation Operation), mode, set temperature, air 
velocity, operation prohibition, ON/OFF of general equipment, output of free contact.   
Up to 10,000 output sources from the ones listed above are selectable.   

z

 

Just as when making the settings for the input source, settings can be copied and pasted 
using Ctrl+C and Ctrl+V key combinations respectively. 
 

Содержание PAC-YG21CDA

Страница 1: ...lling the Table Setting Tool 5 3 3 Starting and Closing the Program 5 4 Screen Configuration and Various Utilities 7 4 1 Screen configuration 8 4 2 Various utilities 9 5 Table Setting 11 5 1 Screen Configuration of Table Setting 11 5 2 Setting the Set File 11 5 3 Setting the Set Value File 12 5 4 Setting the Table File 13 5 5 Selecting the Drive of ATA Card 21 5 6 Writing in ATA Card 21 6 Option S...

Страница 2: ...ion for use given to our customer by Mitsubishi Electric Corporation By using this software the user agrees to the conditions of the License Mitsubishi Electric and associated suppliers are not responsible for any collateral secondary or special damages even if notified by the distributor of the possibility of a certain type of damage Mitsubishi Electric is not responsible for any rights claimed b...

Страница 3: ... latest version of PLC in combination with the latest version of Table Setting Tool 2 The temperature unit displayed must be the same in one system Some screens used in this Manual provide just an image differing from actual appearance Unless otherwise specified G 50A in this manual refers to both G 50A and GB 50A 2 2 Expressions in This Manual Unless designated Windows 2000 Professional and Windo...

Страница 4: ... countries or its subsidiary 2 4 Image of Using Tool By using this table setting tool the number of G 50A to be controlled the output signal format the relationship between the input and the output may be set Save the set content into ATA card and insert the ATA card to the sequencer for use Use the adapter Table setting tool ATA card with the setting content written For the installation method of...

Страница 5: ...up exe After double clicked the dialog shown on the right will appear on screen Click Next to proceed with installing Table Setting Tool and advance to the next dialog 2 The screen to confirm the folder to be installed is displayed Clicking NEXT starts installing The destination folder address is C PLCTool 3 Select the unit used for temperature display Centigrade Fahrenheit Click NEXT after select...

Страница 6: ... point to Settings and click Control Panel to open Control Panel 2 Double click Add Remove Programs displayed in the Control Panel window A list of installed programs will appear Click PLCtool and click Remove to uninstall Table Setting Tool 3 3 Starting and Closing the Program 1 To start the program select Program Table Setting Tool of PLC for General Equipment PLCTool from the Start menu and cli...

Страница 7: ...6 3 To close the program click File then Exit from the Table Setting Tool menu ...

Страница 8: ...neral equipment this setting is required even when interlock control is not used Default setting is A contact pulse Pulse width is 1sec Pattern 1 A contact pulse sec sec pulse width Pattern 2 B contact pulse sec sec pulse width Patter 3 level The pulse width can be set to any arbitrary value in 0 1 sec increments Table 4 2 Setting the signal output format Type of Control Settings on the Table Sett...

Страница 9: ...ous settings To execute various settings click the item desired to set at the setting sub menu section and enter the set data on the setting screen displayed This screen is called Initial screen On the menu bar various utilities can be executed such as to save or read the setting data Menu bar Allow you to prepare or overwrite files and check the version Setting menu pane Setting sub menu pane Mas...

Страница 10: ...ng setting data 1 To save the setting data to a directory in which data was saved the last time or a directory from which the data was read click File Save All set data will be saved An alarm message will appear if any of the following three items is skipped SET CSV PARA CSV TABLE BIN If there is no need to change the settings in the menus such as PARA CSV proceed to the next step 2 To save to a d...

Страница 11: ...lp About Version 2 Click Help Help when you want to view this operation manual The help screen will appear To view this manual you need Adobe Systems Incorporated s Acrobat Reader Version 5 0 or later Note Acrobat is a registered trademark of Adobe Systems Incorporated System button The screen of system information can be displayed Notice z The system information collects configuration information...

Страница 12: ... is set to 0 set The case without G 50A connection 0 set only applies to operating monitoring the general equipment at PLC side 2 After finishing the setting click the OK button The set detail is saved to back to the initial screen Clicking the Cancel button returns to the initial screen without saving the set detail 5 Table Setting Table setting For setting change of table display writing into AT...

Страница 13: ...s to the initial screen without saving the set detail Selecting the connecting number of G 50A Select the connecting number of G 50A to be controlled The set value ranges from 0 to 2 sets Select 1set 2sets to perform the interlock control OK button For saving the set detail Cancel button For returning to initial screen without saving set detail OK button For saving of set detail Cancel button For ...

Страница 14: ...cel button returns to the initial setting screen without saving the set detail Notice z The setting of input output relations is to set the relationship between the input and output representing an event operation to operate the output of certain equipment when the input condition of the equipment changes Next button For advancing to the next setting screen Cancel button For returning to the initi...

Страница 15: ... that is 1 larger than the one in the copy source Use these functions to make the same settings for multiple pieces of equipment Example When the settings in the first row are copied and pasted in the second row the equipment number under Classification 2 in the second row will automatically change to No 2 If the number under Classification 2 in a certain row in the copy source is set to the maxim...

Страница 16: ...n without saving the set detail Clicking the Back button returns to the former setting screen Next button For advancing to the next setting screen Cancel button For returning to initial setting screen without saving set detail 1 Setting the output source number First the number of objective output sources are set Can be set up to 10 000 maximum 2 Selecting the output source The output source objec...

Страница 17: ...he column of No you may select from the output source previously set 6 Set all input output relation numbers as 2 5 above 7 After finishing the setting click the Finish button The set detail is saved to return to the initial screen Clicking the Cancel button returns to the initial setting screen without saving the set detail Clicking the Back button returns to the former setting screen Finish butt...

Страница 18: ...d as the candidates Select the function being provided to the actual equipment z The candidates of input and output sources unused will be deleted at completion of the setting of the table file Setting with the candidates of the input or output source is required again z Settings for the output content can be copied and pasted with Ctrl C and Ctrl V key combinations z Settings for the output conte...

Страница 19: ...To cancel the selection click the Cancel button Figure 5 7 Selecting screen of input source At selecting the No column of output source Clicking the cell of the No column of output source displays the contents set on the selecting screen of output source You may select the output source from the candidates 1 Clicking the cell of the No column displays the screen to select output source 2 Click the...

Страница 20: ...for input and 3 points for output Setting of DIP SW of indoor unit is required SW1 9 10 ON Table 5 2 Input and output for the free contact of indoor unit No Items Detail 1 Free contact input No 1 CN32 2 port 2 Free contact input No 2 CN32 3 port 3 Free contact input No 3 CN51 2 port 4 Free contact input No 4 CN51 5 port 5 Free contact output No 1 CN52 2 port 6 Free contact output No 2 CN52 3 port ...

Страница 21: ...tatus Output source in input output No a b c a Indicates the input source No input output relation No b Indicates the output source No c Indicates the content of the input source 3 Error message for unused sources When the input or output source being not used for the input output relation setting is existed the error message below will be displayed Supplement The input source of General equipment...

Страница 22: ...ng in ATA Card Clicking Writing in ATA card of the setting sub menu allows you to write the detail being set to ATA card Figure 5 10 Initial screen 1 Set PC card being inserted with ATA card to the drive 2 Clicking Writing ATA card of the setting sub menu displays a massage to confirm After confirming the message detail write the set detail in ATA card At completion of the writing a message to fin...

Страница 23: ... hardware in the task bar to display and then select it On the Unplug or Eject Hardware screen select the device desired to remove and click Stop Then the screen to confirm is displayed After confirming the screen display prepare for the removal of the PC card ...

Страница 24: ...the setting sub menu displays the screen to read the set detail from ATA card The data being set to ATA card can be read in Figure 6 2 Setting screen to read from ATA card 6 Option Setting Option setting For reading of set detail from ATA card Reading from ATA card For reading out of set detail inside ATA card Figure 6 1 Initial screen Selecting the drive For selecting the drive to mount ATA card ...

Страница 25: ...ead the set detail from ATA card Clicking the NO button returns to the initial screen without reading from ATA card 3 To remove PC card in safe right click Unplug or eject hardware in the task bar to display for selection On the Unplug or eject hardware screen select the device desired to remove and click Stop Then the screen to confirm is displayed After confirming the screen display prepare for ...

Страница 26: ...nt control Question Answer Remarks How to confirm the version of the table setting tool Select the menu Help Version of the table setting tool displays the version in question What is the measure to be taken when the output setting exceeds a certain input For one input output relation setting the output setting of 50 maximum is provided For the output setting number of over 51 set the same input b...

Страница 27: ...MULTI S series Is it possible to use GB 50A Yes it is Read this manual changing the word from G 50A to G 50A GB 50A The license for PLC for General Equipment must be registered on G 50A GB50A Only Ver 2 90 or later of GB 50A is released The 1ºF temperature setting function is available only on Ver 3 00 or later The temperature setting by 1ºF increment on the PLC of PAC YG21CDA is necessary Which c...

Страница 28: ...WT04265X04 HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Отзывы: