12
Figure 5-2. Setting screen of set file
5-3 Setting PARA.CSV file
Clicking [Setting PARA.CSV file] displays the screen for the output format setting of general equipment. On
this screen, the output format and pulse width are set for the DO unit of general equipment at PLC side.
Figure 5-3. Setting screen of set value file
(1) The output format is selected for each general equipment, and the pulse width is selected in the case
of pulse.
* The default value is set to [A-contact pulse, 1s]. For the pulse width, numerical input can be performed in addition to
selecting the candidate value (From 0.1 to 99.9).
(2) After finishing the setting, click the [OK] button. The set detail is saved to return to the initial screen.
*Clicking the [Cancel] button returns to the initial screen without saving the set detail.
Selecting the connecting
number of G-50A
Select the connecting number of
G-50A to be controlled. The set
value ranges from 0 to 2 sets.
(Select "1set/2sets” to perform
the interlock control.)
[OK] button
For saving the set detail
[Cancel] button
For returning to initial screen
without saving set detail
[OK] button
For saving of set detail
[Cancel] button
For returning to initial screen
without saving set detail
Selecting the operating
pulse width
In case of pulse, select the pulse
width. [0.1, 0.5, 1, 5, 10s]
Selecting the stopping
pulse width
In case of pulse, select the pulse
width. [0.1, 0.5, 1, 5, 10s]
Selecting the stopping
output format
Select the output format at
operating side. [Level] [A-contact
pulse] [B-cont
act pulse]
Selecting the operating output format
The output format at operating side is selected.
[Level] [A-contact pulse] [B-contact pulse]
*Selecting the level makes the stopping side
level also.