4.3. Space required for installation and servicing
1
. The space when installing with the suspension bolts.
(1) Front View (Fig. 4-6)
A
Branch box
B
On the side of piping
(2) Side View (Fig. 4-7, Fig. 4-8, Fig. 4-9)
C
For indoor installations
D
Ceiling board
E
Maintenance hole
F
Reactor Box (Optional parts)
*1: Minimum 350 mm is required for 90° bends in refrigerant piping.
*2: is “Min. 200 mm” <recommendation>.
In the case of less than 200 mm (for example is 100 mm), the exchange work
of Branch box from a maintenance hole becomes dif
fi
cult (Only exchange work
of a PCB, linear expansion valve coils and sensors are possible).
To install the optional Reactor Box, set to Min. 270 mm <recommendation>
(Fig. 4-9).
In the case of “ 450 mm”, prepare a maintenance hole at a PCB side (as it is
shown in Fig. 4-8, Fig. 4-9), and “Min. 300 mm” is needed as distance .
In the case of less than 300 mm (for example is 100 mm), the exchange work
of Branch box, linear expansion valve coils and sensors from a maintenance
hole becomes dif
fi
cult (Only exchange work of a PCB is possible).
(3) Top View (Fig. 4-10)
2
. The space when installing on the
fl
oor. (Fig. 4-11)
3
. The space when installing on a wall. (Fig. 4-12)
Warning:
The installation direction is limited when installing on a wall. (Fig. 4-13)
Correct installation
direction
When installing the unit on
the wall, install the piping
connected to the outdoor
unit facing down. Other ways
are not acceptable.
When installing on the wall, do not place
the device in the manner shown below.
Doing so may cause electric shock or fire.
*3: is “ 600 mm” <recommendation>.
5. Refrigerant piping
* Always follow the speci
fi
cations written in the installation manual of the outdoor unit. Exceeding these requirements may cause reduced performance of the equipment,
and malfunctions.
(3)
Min. 250
Fig. 4-10
(1)
(2)
50
450
450
250
250
250
170
30
278
180-200
*1
*3
*2
Fig. 4-6
Fig. 4-7
Fig. 4-8
4. Dimensions and required servicing space of Branch Box
Fig. 4-11
Fig. 4-13
Fig. 4-12
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
450
Fig. 4-9
(mm)