14
• The water velocity in pipes should be kept within certain limits of material to avoid erosion, corrosion and excessive
noise generation.
Be aware, and take care of , that local velocities in small pipes, bends and similar obstructions can exceed the values
of previous page.
e.g.) Copper : 1.5 m/s
Warning
• Use clean enough water which meets water quality standards. The deterioration of water quality may result in the sys-
tem breakdown or the water leakage.
• Never use anything other than water as a medium. It may cause a
fi
re or an explosion.
• Do not use heated or cooled water that is produced by the air to water heat pump directly for drinking or cooking.
There is a risk to damage your health. There is also a risk that installing the water heat exchanger may corrode if the
necessary water quality for air to water heat pump system cannot be maintained. If you wish to use the heated or
cooled water from the heated pump for these purposes, take measure such as to the second heat exchanger within
the water piping system.
Reference data
Required speci
fi
cation and performance of Plate Heat Exchanger.
Required speci
fi
cation
Refrigerant side
Refrigerant type
R410A
Normal (designed) pressure
4.15MPa
Operating temperature
-20~100
:
Water side
Refrigerant type
Clean water
Normal (designed) pressure
1.5MPa
Operating temperature
-20~90
:
(No freezing)
Burst pressure
12.45MPa (4.15MPa ×3) or more
Frozen performance
Satisfy an initial performance since 5 times or more of deep freezing.
Heat cycle
70,000 times or more…Temperature difference: about 50K
Endurance pressure
72,000 times or more…Pressure difference: 3.3MPa (0
↔
3.3MPa)
Required performance
< For 2.5~3 HP >
Required performance of Plate Heat Exchanger
kW
9.0
9.0
Refrigerant side
(R410A)
Inlet temperature
degC
75
100
Gas pipe:
[
12.7 mm
Condensing temperature
degC
39.5
63.5
Liquid pipe:
[
9.52 mm
Subcool
degC
2
2
Max. pressure loss
kPa
50
50
Water side
Inlet temperature
degC
30
55
Inlet / outlet pipe:
[
28.6 mm
Outlet temperature
degC
35
60
Water
fl
ow volume
L/min
25.8
25.8
Max. pressure loss
kPa
50
50
* For heating mode, used at counter
fl
ow direction between refrigerant
fl
ow and water one.
< For 4~6 HP >
Required performance of Plate Heat Exchanger
kW
14.0
14.0
Refrigerant side
(R410A)
Inlet temperature
degC
75
100
Gas pipe:
[
15.88 mm
Condensing temperature
degC
39.5
63.5
Liquid pipe:
[
9.52 mm
Subcool
degC
2
2
Max. pressure loss
kPa
50
50
Water side
Inlet temperature
degC
30
55
Inlet / outlet pipe: over
[
28.6 mm
Outlet temperature
degC
35
60
Water
fl
ow volume
L/min
40.1
40.1
Max. pressure loss
kPa
50
50
* For heating mode, used at counter
fl
ow direction between refrigerant
fl
ow and water one.