31
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
< Thermistor for lower temperature >
Temperature (
)
Resistance (k
)
<Thermistor Characteristic graph>
Thermistor for
lower temperature
Target temperature thermistor (TH1)
Pipe temperature thermistor/liquid (TH2)
Pipe temperature thermistor / 2-phase (TH5)
Thermistor R0 =15k
"
± 3%
Fixed number of B =3480
± 2%
Rt =15exp { 3480 (
1
273+t
–
1
273
) }
0
:
15k
"
10
:
9.6k
"
20
:
6.3k
"
25
:
5.4k
"
30
:
4.3k
'
40
:
3.0k
"
Input
SW 1-1 SW 1-2 SW 1-3 SW 6-1 SW 6-2 Step for capacity setting
REMOTE SWITCH
Type A (4bit-8 setting)
OFF
OFF
OFF
OFF
OFF
OFF/Step1/Step2/…/Step7/Auto step
REMOTE SWITCH
Type B (1bit-1 setting)
ON
OFF
OFF
OFF
OFF
OFF/Step1/Step4/Step7/Auto step
4-20mA
ON
ON
OFF
ON
ON
OFF/Step1/Step2/…/Step7
1-5V
ON
ON
OFF
OFF
ON
OFF/Step1/Step2/…/Step7
0-10V
OFF
OFF
ON
OFF
OFF
OFF/Step1/Step2/…/Step7
0-10k
Ω
ON
OFF
ON
OFF
OFF
OFF/Step1/Step2/…/Step7/Auto step
No input (AUTO mode)
OFF
ON
ON
OFF
OFF
Only Auto step mode
SW1-4~8 : OFF
fi
xed (Initial setting)
• SW2-1/2-2 : Fixed operation mode
SW2-1
SW2-2
Details
OFF
OFF
Not FIX (Depending on Remote controller setting)
ON
OFF
[Cooling]FIX
OFF
ON
[Heating]FIX
ON
ON
External input (Depending on TB142-3,4)
• SW2-3/2-4/2-5 : Fixed set temperature [For Auto step mode only]
SW2-3
SW2-4
SW2-5
Details
OFF
OFF
OFF
Not
fi
xed (Remote controller setting)
ON
OFF
OFF
Cooling 19
˚
C /Heating 17
˚
C FIX
OFF
ON
OFF
20
˚
C FIX
ON
ON
OFF
22
˚
C FIX
OFF
OFF
ON
24
˚
C FIX
ON
OFF
ON
26
˚
C FIX
OFF
ON
ON
28
˚
C FIX
ON
ON
ON
Cooling 30
˚
C / Heating 28
˚
C FIX
Set switches in case of auto step mode.
SW2-6 : Setting of TH5
When TH5 (2-phase pipe temp. thermistor) is connected, it is necessary to set the Dip SW2-6 of the interface controller.
SW2-6
Details
OFF
Connect TH5
ON
Not connect TH5 (Initial setting)
SW2-7, 8 : OFF
fi
xed (Initial setting)
SW3 : LED2~5 display setting (Refer to 8.)
5. Interface controller switch setting
Set the switches following the system speci
fi
cations below.
Switch1. Switch6 : Input selection of inverter capacity setting
Содержание PAC-IF012B
Страница 95: ...95 ...