32
Demand control is available by connecting remote switches with termi-
nal No.10 - 14.
Make sure to use the non-voltage switch (for the remote switch).
Remote switch cable length : Maximum 10m
Remote switch : Minimum applicable load DC12V, 1mA
• 4-20mA / 1-5V / 0-10V / 0-10k
Ω
1
Use 4-20mA / 1-5V / 0-10V
Connect the transmission cables to No. 3 and 4 on the terminal
block (TB62).
No. 3 on the terminal block (TB62) : Plus side
No. 4 on the terminal block (TB62) : Minus side (Reference side)
2
Use adjustable resistor (0-10k
Ω
)
Connect the transmission cables to No. 1 and 2 on the terminal
block (TB62).
Adjust-
able resistor
(0-10k
Ω
)
4-20mA
1-5V
0-10V
Step for
capacity
setting
Remark
0~100
Ω
4~5mA
0~1.25V
0~0.63V
OFF 0%
Stop
510
Ω
7mA
1.75V
1.88V
Step1 10%
Fixed capacity
(Hz
fi
xed) mode
1k
Ω
9mA
2.25V
3.13V
Step2 20%
2k
Ω
11mA
2.75V
4.38V
Step3 30%
3.3k
Ω
13mA
3.25V
5.63V
Step4 50%
4.3k
Ω
15mA
3.75V
6.88V
Step5 70%
5.6k
Ω
17mA
4.25V
8.13V
Step6 80%
7.5k
Ω
19~20mA 4.75~5V
9.38~10V Step7 100%
10k
Ω
–
–
–
Auto step
Auto step mode
OPEN(12k
Ω
~) –
–
–
OFF 0%
Stop
*The values of the above table show the mid-point of each step range.
Tolerance : 0-10k
Ω
: ±5%
4-20mA : ±0.4mA
1-5V : ±0.1V
0-10V : ±0.2V
Cable length : Maximum 10m
6. Input speci
fi
cations
Demand control is available by external input.
It is possible to set the outdoor unit’s power consumption by setting the switch of the interface controller.
• REMOTE SWITCH Type A (4bit - 8 setting) / Type B (1bit -1 setting)
Step for capacity setting
TB142
10-11
(COM-IN5)
TB142
10-12
(COM-IN6)
TB142
10-13
(COM-IN7)
TB142
10-14
(COM-IN8)
Remark
Auto step mode
OFF
Fixed capacity
(Hz fixed)
mode
TB142
I/F
10
11
12
13
14
10
11
12
13
14
At site
4 bit 8 switch
OFF~AUTO step
TB142
I/F
At site
Step1
Step4
Step7
AUTO step
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF 0%
Step1 10%
Step2 20%
Step3 30%
Step4 50%
Step5 70%
Step6 80%
Step7 100%
Auto step
OFF 0%
Step1 10%
Step4 50%
Step7 100%
Auto step
[OFF]
[ON]
[OFF]
[ON]
TypeA
TypeB
{
Photo. 6-1
TB142
TB62