3. Electrical work
3.1.5. Connecting External Output
The signal in the following states can be output.
TB141 Item OFF
ON
1-2
(OUT1)
X1
Operation Output
OFF
ON
3-4 (OUT2)
X2
Error
Output
Normal
Error
5-6
(OUT3)
X3 Comp. Output
OFF(Comp. OFF) ON
(Comp. ON)
7-8 (OUT4)
X4
Defrost
Output
OFF
ON (Defrosting)
9-10 (OUT5)
X5
Mode(Cool)
Output
OFF
ON (Cooling)
11-12 (OUT6)
X6 Mode(Heat)
Output
OFF
ON (Heating)
13-14 (OUT7)
–
–
–
–
Cable length : Maximum 50m
Output speci
fi
cation : Non-voltage switch 1A or less , 240V AC
*Connect the surge absorber according to the load at site.
2
1
3
5
4
6 7 8
TB141
9 10 11 12 13 14
X1
I/F
At site
X2 X3 X4 X5 X6
Note : External output signals are separated by basic insulation from other circuit of
interface.
Caution : When 2 or more external outputs are used, the power supply on the output
side should be the same.
3.1.7. Switch setting
It is possible to set the following function by setting the switch of the interface controller.
Set switches in case of auto mode.
Photo.3-6
TB141
3.1.6. Wiring speci
fi
cation External output / External input
Locally supplied parts
Item
Name
Model and speci
fi
cations
External output function External output signal wire Use sheathed vinyl coated cord or cable.
Wire type :
CV, CVS or equivalent.
Wire size :
Stranded wire 0.5mm
2
to 1.25mm
2
Solid wire:
{
0.65mm to
{
1.2mm
Display lamp, etc.
Non-voltage Contact AC220-240V (DC30V), 1A or less
External input function
External input signal wire
Use sheathed vinyl coated cord or cable.
Wire type :
CV, CVS or equivalent.
Wire size :
Stranded wire 0.5mm
2
to 1.25mm
2
Solid wire :
{
0.65mm to
{
1.2mm
Switch
Non-voltage "a" contact
3.1.8.Before test run
After completing installation and the wiring and piping of the local application and outdoor units, check for refrigerant leakage, looseness in the power supply or control
wiring, wrong polarity, and no disconnection of one phase in the supply.
Use a 500-volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1.0M
Ω
.
Warning:
Do not use the system if the insulation resistance is less than 1.0M
Ω
.
Caution:
Do not carry out this test on the control wiring (low voltage circuit) terminals.
SW2-1
SW2-2
Details
OFF
OFF
Not FIX (Depending on Remote controller setting)
ON
OFF
[Cooling] FIX
OFF
ON
[Heating] FIX
ON
ON
External input (Depending on TB142-3, 4)
• SW2-1/2-2 : Fixed operation mode
SW2-3
SW2-4
SW2-5
Details
OFF
OFF
OFF
Not
fi
xed (Remote controller setting)
ON
OFF
OFF
Cooling 19°C/Heating 17°C FIX
OFF
ON
OFF
20°C FIX
ON
ON
OFF
22°C FIX
OFF
OFF
ON
24°C FIX
ON
OFF
ON
26°C FIX
OFF
ON
ON
28°C FIX
ON
ON
ON
Cooling 30°C/Heating 28°C FIX
• SW2-3/2-4/2-5 : Fixed set temperature [For Auto mode only]
SW2-6
Details
Model
OFF
Effect
PAC-IF012B-E
ON
No effect
PAC-IF011B-E
• SW2-6 : COND./EVA. TEMP. THERMISTOR (TH5)
7
GB