3. Electrical work
3.1.4. Connecting external input
Demand control is available by external input.
It is possible to set the outdoor unit’s power consumption by setting the switch of the interface controller.
• REMOTE SWITCH Type A (4bit - 8 setting) / Type B (1bit -1 setting)
Demand control is available by connecting remote switches with terminal No.10 - 14.
Make sure to use the non-voltage switch (for the remote switch)
Remote switch cable length : Maximum 10m
Remote switch : Minimum applicable load DC12V, 1mA
• 4-20mA / 1-5V / 0-10V / 0-10k
Ω
1
Use 4-20mA / 1-5V / 0-10V
Connect the transmission cables to No. 3 and 4 on the terminal block (TB62).
No. 3 on the terminal block(TB62) : Plus side
No. 4 on the terminal block(TB62) : Minus side (Reference side)
2
Use adjustable resistor (0-10k
Ω
)
Connect the transmission cables to No. 1 and 2 on the terminal block (TB62).
Adjustable
resistor
(0-10k
Ω
)
4-20mA
1-5V
0-10V
Step for
capacity
setting
Remark
0~100
Ω
4~5mA
0~1.25V
0~0.63V
OFF 0% Stop
510
Ω
7mA
1.75V
1.88V
Step1 10%
Hz
fi
xed
mode
1k
Ω
9mA
2.25V
3.13V
Step2 20%
2k
Ω
11mA
2.75V
4.38V
Step3 30%
3.3k
Ω
13mA
3.25V
5.63V
Step4 50%
4.3k
Ω
15mA
3.75V
6.88V
Step5
70%
5.6k
Ω
17mA
4.25V
8.13V
Step6 80%
7.5k
Ω
19~20mA
4.75~5V
9.38~10V
Step7 100%
10k
Ω
–
–
–
Auto
Auto mode
OPEN(12k
Ω
~)
–
–
–
OFF 0% Stop
*The value of the above-mentioned table becomes the center of the input value.
Cable length : Maximum 10m
Step for capacity setting
TB142
10-11
(COM-IN5)
TB142
10-12
(COM-IN6)
TB142
10-13
(COM-IN7)
TB142
10-14
(COM-IN8)
Remark
Auto mode
OFF
Hz fixed
mode
TB142
I/F
10
11
12
13
14
10
11
12
13
14
At site
OFF
〜
AUTO
TB142
I/F
At site
Step1
Step4
Step7
AUTO
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF 0%
Step1 10%
Step2 20%
Step3 30%
Step4 50%
Step5 70%
Step6 80%
Step7 100%
Auto
OFF 0%
Step1 10%
Step4 50%
Step7 100%
Auto
[OFF]
[ON]
[OFF]
[ON]
TypeA
TypeB
{
Input
SW 1-1 SW 1-2 SW 1-3 SW 6-1 SW 6-2
Step for capacity setting
REMOTE SWITCH
Type A (4bit-8 setting)
OFF
OFF
OFF
OFF
OFF
OFF/Step1/Step2/…/Step7/Auto
REMOTE SWITCH
Type B (1bit-1 setting)
ON
OFF
OFF
OFF
OFF
OFF/Step1/Step4/Step7/Auto
4-20mA
ON
ON
OFF
ON
ON
OFF/Step1/Step2/…/Step7
1-5V
ON
ON
OFF
OFF
ON
OFF/Step1/Step2/…/Step7
0-10V
OFF
OFF
ON
OFF
OFF
OFF/Step1/Step2/…/Step7
0-10k
Ω
ON
OFF
ON
OFF
OFF
OFF/Step1/Step2/…/Step7/Auto
No input (AUTO mode)
OFF
ON
ON
OFF
OFF
Only Auto mode
Switch1, Switch 6 : Input selection of inverter capacity setting
Photo.3-5
TB142
• External function setting
This function is setting operation mode or stopping compressor, by the external signal.
TB142
Item
OFF
ON
Remark
1-2 (IN1)
Forced Comp. OFF
Normal
Forced Comp. OFF
3-4 (IN2)Item Fixed operation mode Cooling Heating
Available when SW2-1 and SW2-2
are ON
Cable length : Maximum 10m
Remote switch : Minimum applicableload DC12V, 1mA
Caution:
The external input signals are separated by basic insulation from power supply for the unit.
The external input signals should be separated by supplementary insulation from where user may touch in case that it is installed where
user may touch.
Connect the terminals by using the ring terminals and also insulate the cables of adjoining terminals when wiring to terminal block.
2
1
3 4
TB142
I/F
At site
I/F
At site
6
5
2
1
4
3
0-10 k
Ω
TB62
4-20mA/1-5V/0-10V
Wired remote controller
(For maintenance)
+
TB62
6
GB