Mitsubishi Netcom User Manual
Rev 3 02/24/2009
49
DESCRIPTION
"This object determines the nature of the action to be
taken at the time when the countdown of the
upsShutdownAfterDelay and upsRebootWithDuration
objects reaches zero.
Setting this object to output(1) indicates that
shutdown requests should cause only the output of the
UPS to turn off.
Setting this object to system(2)
indicates that shutdown requests will cause the entire
UPS system to turn off."
::= { upsControl 1 }
upsShutdownAfterDelay OBJECT-TYPE
SYNTAX
INTEGER
-- UNITS seconds
ACCESS
read-write
STATUS
mandatory
DESCRIPTION
"Setting this object will shutdown (i.e., turn off)
either the UPS output or the UPS system (as determined
by the value of upsShutdownType at the time of
shutdown) after the indicated number of seconds, or
less if the UPS batteries become depleted. Setting
this object to 0 will cause the shutdown to occur
immediately.
Setting this object to -1 will abort the
countdown.
If the system is already in the desired
state at the time the countdown reaches 0, then
nothing will happen.
That is, there is no additional
action at that time if upsShutdownType = system and
the system is already off.
Similarly, there is no
additional action at that time if upsShutdownType =
output and the output is already off.
When read,
upsShutdownAfterDelay will return the number of
seconds remaining until shutdown, or -1 if no shutdown
countdown is in effect.
On some systems, if the agent
is restarted while a shutdown countdown is in effect,
the countdown may be aborted.
Sets to this object
override any upsShutdownAfterDelay already in effect."
::= { upsControl 2 }
upsStartupAfterDelay OBJECT-TYPE
SYNTAX
INTEGER
-- UNITS seconds
ACCESS
read-write
STATUS
mandatory
DESCRIPTION
"Setting this object will start the output after the
indicated number of seconds, including starting the
UPS, if necessary.
Setting this object to 0 will
cause the startup to occur immediately.
Setting this
object to -1 will abort the countdown.
If the output
is already on at the time the countdown reaches 0,
then nothing will happen.
Sets to this object
override the effect of any upsStartupAfterDelay
countdown or upsRebootWithDuration countdown in
progress.
When read, upsStartupAfterDelay will return
the number of seconds until startup, or -1 if no
startup countdown is in effect.
If the countdown