Mitsubishi Netcom User Manual
Rev 3 02/24/2009
34
upsIdentAgentSoftwareVersion OBJECT-TYPE
SYNTAX
DisplayString
ACCESS
read-only
STATUS
mandatory
DESCRIPTION
"The UPS agent software version.
This variable may or may
not have the same value as upsIdentUPSSoftwareVersion in
some implementations."
::= { upsIdent 4 }
upsIdentName OBJECT-TYPE
SYNTAX
DisplayString
ACCESS
read-write
STATUS
mandatory
DESCRIPTION
"A string identifying the UPS.
This object should be
set by the administrator."
::= { upsIdent 5 }
upsIdentAttachedDevices OBJECT-TYPE
SYNTAX
DisplayString
ACCESS
read-write
STATUS
mandatory
DESCRIPTION
"A string identifying the devices attached to the output
of the UPS.
This object should be set by the
administrator."
::= { upsIdent 6 }
upsBattery OBJECT IDENTIFIER ::= { MitsubishiUPS 2 }
upsBatteryStatus OBJECT-TYPE
SYNTAX
INTEGER
{
unknown(1),
batteryNormal(2),
batteryLow(3),
batteryDepleted(4)
}
ACCESS
read-only
STATUS
mandatory
DESCRIPTION
"The indication of the capacity remaining in the UPS
batteries.
A value of batteryNormal indicates a normal battery
condition.
A value of batteryLow indicates the remaining battery run-
time
will not maintain the output load for an extended period of
time.
A value of batteryDepleted indicates that the UPS will be
unable
to sustain the present load when and if the utility power
is lost."
::= { upsBattery 1 }