9-2. R.V. COIL CONTROL
R.V. COIL CONTROL MUZ-HJ25VA MUZ-35VA
Heating . . . . . . . . . . . . . . . . . OFF
Cooling . . . . . . . . . . . . . . . . . ON
Dry . . . . . . . . . . . . . . . . . . . . ON
NOTE:
The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan
motor
Compressor
5 seconds
15 seconds
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
9-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
9-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor
Purpose
Actuator
Compressor
LEV
Outdoor fan
motor
R.V. coil
Indoor fan
motor
Discharge temperature thermistor
Protection
○
○
Indoor coil temperature thermistor
Cooling: Coil frost prevention
○
Heating: High pressure protection
○
Defrost thermistor
Cooling: High pressure protection
○
○
○
Heating: Defrosting
○
○
○
○
○
Fin temperature thermistor
Protection
○
○
9
ACTUATOR CONTROL
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
R.V. COIL CONTROL MUZ-HJ50VA MUZ-HJ60VA MUZ-HJ71VA
Heating . . . . . . . . . . . . . . . . . ON
Cooling . . . . . . . . . . . . . . . . . OFF
Dry . . . . . . . . . . . . . . . . . . . . OFF
NOTE:
The 4-way valve reverses for 5 seconds right before start-up of the compressor.
OBH648F
Содержание MSZ-HJ VA Series
Страница 12: ...12 MUZ HJ25VA E1 ER1 ET1 6 WIRING DIAGRAM MUZ HJ25VA E2 ER2 ET2 OBH648F ...
Страница 13: ...13 MUZ HJ35VA E1 ER1 ET1 MUZ HJ35VA E3 ER3 ET2 OBH648F ...
Страница 14: ...14 MUZ HJ50VA E1 ER1 ET1 MUZ HJ50VA E2 ER2 ET2 MUZ HJ60VA E2 MUZ HJ71VA E2 OBH648F ...
Страница 15: ...15 MUZ HJ60VA E1 ER1 ET1 MUZ HJ71VA E1 ER1 ET1 OBH648F ...
Страница 65: ...65 OBH648F ...