3-1. OPERATING RANGE
(1) POWER SUPPLY
Rated voltage
Guaranteed voltage (V)
Indoor unit
208/230 V
1 phase
60 Hz
Min. 187
208
230 Max. 253
(2) OPERATION
Mode
Condition
Intake air temperature (°F)
Indoor
Outdoor
DB
WB
DB
WB
Cooling
Standard temperature
80
67
95
—
Maximum temperature
90
73
115
—
Minimum temperature
67
57
14
—
Maximum humidity
78%
—
Heating
Standard temperature
70
60
47
43
Maximum temperature
80
67
75
65
Minimum temperature
70
60
14
13
3-2. OUTLET AIR SPEED AND COVERAGE RANGE
Model
Mode
Function
Airflow
(CFM)
Air speed
(ft./sec.)
Coverage
range (ft.)
MSZ-D30NA
MSZ-D36NA
HEAT
Dry
848
23.6
45.0
MSZ-D30NA
MSZ-D36NA
MSY-D30NA
MSY-D36NA
COOL
Dry
848
23.6
45.0
Wet
763
21.3
40.7
● The air coverage range is the figure up
to the position where the air speed is 1
ft./sec., when air is blown out horizon-
tally from the unit properly at the High
speed position.
The coverage range should be used
only as a general guideline since it var-
ies according to the size of the room
and furniture arranged inside the room.