The JA-65ST wireless combined smoke and heat detector 

 The JA-65ST wireless combined smoke and heat detector  

 

MLW51503 

The JA-65ST is a wireless component of the JABLOTRON ALARMS 

PROFI

 and 

MAESTRO

 security systems. It is used to detect fire hazards 

in the interior of residential or commercial buildings. It is not designed to 

be installed in industrial premises. The JA-65ST  detector uses wireless 

communication and it is powered with three AA 1.5V alkaline batteries. 

The JA-65ST consists of two independent detectors – an optical smoke 

detector and a heat detector. The optical smoke detector works on the 

principle of scattered  light and is very sensitive to large dust particles 

which are present in dense smoke. It is less sensitive to smaller particles 

generated by the combustion of liquids such as alcohol. That is why there 

is also a built-in heat detector which has a slower reaction but is much 

better at detecting fire which generates heat quickly with a small amount 

of smoke. The microprocessor performs digital analysis of these values 

which markedly increases false alarm immunity. 

Detector range 

The smoke detector must be installed so that any smoke easily drifts 

into the detector, e.g. on the ceiling. It is suitable for residential buildings 

but not suitable for free spaces, outdoor environments or interiors with 

extremely high ceilings (above 5 m) where fire by-products can disperse 

over a large area – the smoke would not reach the detector position. 

The detector must always be placed in the section leading to the exit of 

the building (escape route), see Figure 1. If the building has a floor area 

greater than 150 m

2

, installation of an additional detector in some other 

suitable place is required, see Fig.2.  

 

1

2

3

3

4

 

Fig 1 

2

1

3

3

4

3

 

Fig 2

 

1-kitchen 
2-living room 
3-bedroom 
4-children’s bedroom 
 
- Minimum security 
- For more security 
 

 

1

3

3
3

 

Fig 3

 

It is recommended to place additional detectors in rooms where people 

sleep and in rooms with an increased risk of fire - see Fig.3. 

Installation on level ceilings 

Place the detector in the centre of the room if possible. The detector 

must not be recessed into the ceiling due to the possible existence of a 

cool air layer on the ceiling. 

Never place the detector in the corner of 

the room though

 (always keep at least a 0.5 m distance from the corner) 

see Fig 4. 

Installation on sloping ceilings 

If the ceiling is not suitable for mounting on a level surface (e.g. a room 

under a roof ridge), the detector can be installed as in Fig. 5 

 

0.5m

TOP

 

Fig 4 

 

0,9 m

 

 

Fig 5

 

centre of the room, best location 

 acceptable location 

Walls, partitions, barriers and lattice ceilings 

The JA-65ST detector must not be installed closer than 0.5 m from 

any wall or partition. 

A narrow room with a width of less than 1.2m 

requires the detector(s) to be placed at a distance of at least one third of 

the room’s width away.  In the case of separating walls (partitions, 

warehouse objects) which do not reach the ceiling, 

the space is 

considered to be fully separated if the gap between the top of the 

separating wall and the ceiling does not exceed 0.3 m.

 A free space 

of at least 0.5m is required under the detector. Any irregularities of the 

ceiling (e.g. girders) exceeding 5 % of the ceiling height shall be 

considered a wall and the above mentioned limitations shall apply. 

 

Ventilation and air circulation 

The detectors must not be installed directly by a fresh air inlet 

(e.g. air conditioning vents).

 In the case of air being supplied through a 

perforated ceiling, each detector must be placed so that no perforation 

hole occurs within 0.6m of the detector.

 

Avoid installing the detector in the following locations:

 

  places with poor air circulation (niches, corners, apexes of A-

shaped roofs, etc.) 

  places exposed to dust, cigarette smoke or steam 

  places with over-intense air circulation (close to ventilators, heat 

sources, air conditioning outlets, etc.) 

  in kitchens and other cooking places (because steam, smoke or oily 

fumes can reduce detector sensitivity). 

  beside fluorescent lights (electrical interference can cause a false 

alarm) 

  in areas with lots of small insects 

Please note: Most false alarms are caused by improper 

detector location.

 

See CEN/TS 54-14 standards for detailed installation guidelines.

 

Installation 

The detector should be installed by a trained technician with a valid 

certificate  issued by an authorized distributor. Abide by the procedures 

recommended in the previous paragraphs. 

 

1

2

3

1400- 00- 0000- 0001

5

4

6

INS

MEM

SMOKE

TEMP

+

-

7

 

Fig 6: 1– detector cover opening; 2 – detector cover closing; 3 – optical status 

signalling; 4 – arrow showing where to insert the detector; 5 – enrollment code;  

6 – configuration terminals; 7 – battery holders    

 

1. 

open the detector cover, by turning it anti-clockwise (1)

 

2. 

attach the removed plastic base

 to the desired place with screws (not 

shown above). 

3. 

set the configuration terminals (6) according to the table below

 

4. 

Proceed  according to the control panel installation manual.  Basic 

procedure:

 

a. 

Switch on the enrollment mode in the control panel. 

 

b.  When you insert the last battery into the detector, the 

enrollment code is sent to the system – its sending is confirmed 

with a short flash of the LED indicator (3). 

c. 

The control panel confirms the enrollment with a flashing of the 

“BATTERY“ LED on the system keypad at the corresponding 

position. 

 

5. 

Insert  the detector into the plastic base.  The detector can be 

inserted in the plastic base in one position only. It is marked with 

arrows (4) on both plastic parts. Close the detector cover by turning 

it clockwise (2). 

 

Detector setting 

 

ON 

Instant alarm

 

OFF

 

smoke (EN 54-7) or 

heat (EN 54-5)

 

OFF

 

Fire alarm

 

OFF

 

ON

 

memory enabled

 

ON

 

smoke only (EN 54-7) 

(not heat)

 

OFF 

memory disabled

 

OFF 

1

2

3

4

INS

MEM

SMOKE

TEMP

 

ON

OFF

 

OFF 

heat only (EN 54-5) (not 

smoke)

 

ON

 

ON 

Both smoke and heat 

(both conditions at the 

same time)

 

ON 

 