Replace LEV
(coil defect)
Replace LEV
Check of linear expansion valve (LEV)
P
• Press RESET button, while pressing OPERATION SELECT button on remote controller.
(All displays on operational display section are ON.) (Refer to right diagram.)
• With remote controller set toward the indoor unit, press OPERATE/STOP button and
confirm one beep tone.
• With remote controller set toward the indoor unit, OPERATE/STOP button and confirm
two beep tones.
Confirm again
that LEV is
operating
Replace outdoor
electronic control P.C.
board.
LEV operates in full-opening
direction.
· Is LEV connector connected?
· Is LEV coil properly fixed to the body?
Heating/Cooling do not operate.
Normal
Do you hear LEV "click,
click·······"?
Do you touch LEV and
feel it vibrate?
Is LEV coil resistance as per
characterictics below?
Do you hear LEV
"click, click·········"?
No
Yes
Yes
Yes
LEV is normal
Yes
Yes
No
No
LEV (CN 724)
WHT(6)–RED(1)
RED(1)–ORE(4)
YLW(5)–BRN(2)
BRN(2)–BLU(3)
resistance
39
"
~56
"
Characteristics of LEV coil
❈
After you have followed the entire flow chart of "Check of linear expansion valve (LEV)", be sure to follow the procedure below.
Replace current limiting resistor.
Check of rush current limiting circuit
O
Outdoor unit does not operate at all or stops immediately due to overcurrent.
NOTE : When the current limiting resistor is open, the rush current limiting relay
may not be working properly. There fore confirm the limiting resistor
works properly after replacing it.
Normal
Does current limiting resistor detect 10
"
?
No
°
Yes
Heating/Cooling do not operate.
1
Press EMERGENCY OPERATION switch.
2
Unplug the power cord and then plug it again.
3
Press RESET button on remote controller.