12
MUZ-A09RV -
MUZ-A12RV -
E1
E1
OUTDOOR UNIT
REFRIGERANT SYSTEM DIAGRAM
7
MSZ-A09RV -
MSZ-A12RV -
E1
E1
INDOOR UNIT
Unit : mm
MAX. REFRIGERANT PIPING LENGTH
Model
MSZ-A09RV-
MSZ-A12RV-
E1
E1
Additional piping
Max. length :mm
A
12
Piping size O.D : mm
Gas
Liquid
Indoor unit
Outdoor unit
9.52
6.35
0.43
0
Length of connecting pipe : m
Refrigerant Piping
Max. length
A
Height difference should be within
5m regardless of which unit,
indoor or outdoor position is high.
w
Max. Height
difference 8m
Indoor
unit
Outdoor unit
MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE (R-410A:g)
Model
MSZ-A09RV-
MSZ-A12RV-
E1
E1
Outdoor unit precharged
1100
Refrigerant piping length (one way)
9m
8m
60
30
Calculation : Xg=30g /m
✕
(A-7)m
Indoor
heat
exchanger
Outdoor
heat
exchanger
Distributor
Flared connection
Room temperature
thermistor
RT11
Indoor coil
thermistor
RT13(sub)
Defrost
thermistor
RT62
Discharge
thermistor
RT61
Flared connection
Stop valve
Stop valve
(with service port)
Capillary tube
Capillary tube
(2 pcs)
Refrigerant flow in cooling
Compressor
Accumulator
Maffler
Muffler
Reversing valve
Refrigerant flow in heating
Refrigerant pipe
[
9.52
(Option)
Refrigerant pipe
[
6.35
(Option)
Indoor coil
thermistor
RT12(main)
Expansion
valve
[
3.0
o
[
2.0
o
200
[
3.0
o
[
2.0
o
300
For additional charging, charge the refrigerant from liquid phase of the gas cylinder.
If the refrigerant inside the cylinder and the outdoor unit.
However, charging the liquid refrigerant all at once may cause the compressor to be locked.
Thus, charge the refrigerant slowly.
11m
10m
120
90
12m
150
7m
0