2. Installation location
■
Indoor units
Install in a room with a floor area of Amin or more, corresponding to refrigerant quantity M (factory-charged refri locally added refrigerant).
* For the factory-charged refrigerant amount, refer to the spec nameplate or installation manual.
For the amount to be added locally, refer to the installation manual.
Install the indoor unit so that the height from the floor to the bottom of the indoor unit is h0.
For wall mounted: 1.8 m or more
For ceiling suspended, cassette and ceiling concealed: 2.2 m or more
For floor standing (PSA-M): 0 m
* There are restrictions in installation height for each model, so read the installation manual for the particular unit.
M [kg]
Amin [m²]
1.0
4
1.5
6
2.0
8
2.5
10
3.0
12
3.5
14
4.0
16
4.5
20
5.0
24
5.5
29
6.0
35
6.5
41
7.0
47
7.5
54
8.0
62
8.5
69
9.0
78
9.5
87
Wall mounted
h0
]
1.8 [m]
Ceiling concealed
Cassette
Ceiling suspended
h0
]
2.2 [m]
h0
]
2.2 [m]
h0
]
2.2 [m]
Case 1: for wall mounted, ceiling suspended, cassette and concealed
M [kg]
Amin [m²]
< 1.84
No requirements
1.84
6
2.0
6
2.5
7
3.0
9
3.5
10
4.0
11
4.5
13
5.0
14
5.5
15
6.0
17
6.5
18
7.0
20
7.5
21
8.0
22
8.5
24
9.0
25
9.5
26
Case 2: for floor standing (PSA-M)
Floor standing (PSA-M)
h0 = 0 [m]
GG79D020H02_01en.indd 6