OC193-39
<How to operate>
To change the air flow direction, press AIR DISCHARGE button.
1
100%
horizontal
2-5 Auto vane control
2
60% downward
and
40% horizontal
3
80% downward
and
20% horizontal
4
100% downward
FILTER
CHECK MODE
TEST RUN
TIMER OFF TIMER
CHECK SET TEMP.
CLOCK AUTO AUTO
START STOP
FAN
SPEED
SWING
AUTO
RETURN
(1) Frequency judgement
When the unit operates for the first time after the circuit breaker turned to ON, the frequency, 50Hz or 60Hz, is judged by
the horizontality sensing switch. If the frequency cannot be judged immediately for some reason, the sensing operation
continues for 10 minutes with the vane motor at ON.
If the frequency cannot be judged yet after 10-minute sensing, the vane motor turns to OFF. But the AIR DISCHARGE
DIRECTION display continues to be indicated.
(2) During cooling operation
When the cooling operation starts, the horizontal discharge is automatically set. However,
the desired discharge among four modes below-listed can be selected with the AIR DIS-
CHARGE UP/DOWN button on the remote controller.
1
100%-horizontal discharge
2
60%-downward and 40%-horizontal discharge
3
80%-downward and 20%-horizontal discharge
4
100%-downward discharge
NOTE: Discharge
2
is available only when the fan speed is HIGH.
<AUTO RETURN>
When discharge “
3
” or “
4
” continues for 1 hour with the fan speed at LOW, the discharge
direction turns to the horizontal discharge automatically.
NOTE1: After that, the discharge “
3
” or “
4
” is available by setting with the remote controller,
and it continues for 1 hour.
NOTE2: If the discharge direction changes from “
3
” or “
4
”, the direction returns to the hori-
zontal discharge when 1 hour has passed since the discharge “
3
” started.
NOTE3: If the discharge direction changes from “
3
” (or “
4
”) to the horizontal discharge, the
1-hour timer to return the horizontal discharge is canceled at that time.
(3) During heating operation
When the heating operation starts, the same discharge direction as was set last time is
chosen automatically. However, the desired discharge can be selected from among four
modes above-mentioned with the remote controller.
However, in the following cases, the discharge direction turns to the horizontal discharge
despite the setting with the remote controller.
When the thermostat turns to OFF
During defrosting operation with the indoor fan stopped
While the indoor fan operates at EXTRA LOW speed in the hot adjustment
(4) During the operation OFF, the auto vane is in the horizontal position.
(5) When the vane motor is out of order or the connector is badly connected, the air discharge display of the remote
controller continues.
<Remote controller display>
1
2
3
4
Changes by pushing the
AIR DISCHARGE
UP/DOWN button: