OC193-53
4. REMOTE ON-OFF AND INDIVIDUAL REMOTE CONTROLS
This method is available to control one unit or any number of units.
The following operations are available by connecting a relay, a timer adapter (PAC-715AD), and remote ON/OFF switch to the
system. Timer adapter (PAC-715AD) is an optional part. Other parts are on the market.
(A) To start all units in order by remote ON-OFF switch
(B) To stop all units simultaneously by remote ON-OFF switch
(C) To switch from the remote ON-OFF control and the individual remote control
4-1 System
Figure 6 shows the case of three units as an example.The same is the case with any number of units.
Remote
controller
Power supply of
control circuit
Remote
ON/OFF
switch
2-wire
remote
controller
cable
Figure 6
Relay box
Timer adapter cables
Timer adapter
PAC-715AD
3. CONTROL USING TWO REMOTE CONTROLLERS
Two remote controllers are available for control of either one unit or a group of units. Units operate according to the latest com-
mand from either of the two remote controllers.
However, before operation, be sure to set one remote controller for "main controller" and the other for "sub controller", using
dip switch SW17-7 of the remote controller.
3-1 How to set SW17-7
(1) For the main remote controller, turn SW17-7 OFF. (See Figure 5.)
(2) For the sub remote controller, turn SW17-7 ON.
3-2 Remote controller LCD indication
(1) The same indications always appear on both the main and sub remote con-
trollers, excepting in the timer operations.
(2) Timer operations can be set with either of the two remote controllers.
However, LCD indication appears only on the remote controller used for timer
settings.
(3) If both remote controllers are set for timer operation with different time-set-
tings, the timer operation of shorter remaining-time is effective.
(4) Self-diagnostic function is available with either of the two remote controllers.
If one of the remote controllers is used for the self-diagnostic function, the
other remote controllers displays the check mode.
If the self-diagnostic function is reset by either of the two remote controllers,
both remote controllers are reset.
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Individual
operation
Multiple operation
Main remote controller
Sub remote controller
Turn SW17-7 ON
Figure 5
Remote controller