OC193-31
5
Coil frost protection
When indoor coil temperature becomes 5°F or below,coil frost protection will proceed as follows.
<Start condition>
After the compressor has been continuously operated for 3 minutes or more,and the indoor coil temperature has been
5°F or below for 3 minutes,the coil frost protection will start.
<Coil frost protection>
Compressor stops for 6 minutes,and then restarts.
lf the start condition is satisfied again during the first 10 minutes of compressor operation,both the indoor and outdoor
units stop,displaying a check code of “P6” on the remote controller.
<Termination conditions>
Coil frost protection is released when the start condition is not satisfied again during the allowance, or when the COOL
mode stops or changes to another mode.
(2) Indoor fan control
Indoor fan speed LOW/HIGH depends on the remote controller setting.
However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller
setting.
( i ) Fan speed LOW/HIGH depends on the remote controller setting regardless of the thermostat ON/OFF.
(ii) Fan speed will remain on LOW if an abnormality in outdoor unit is detected. (5 minutes)
NOTE : Fan stops immediately if the unit stops or the check mode is started.
(3) Auto vane control
(
1
) Frequency judgement
When the unit operates for the first time after the circuit breaker turned to ON, the frequency, 50Hz or 60Hz, is judged by
the horizontality sensing switch. If the frequency cannot be judged immediately for some reason, the sensing operation
continues for 10 minutes with the vane motor at ON.
If the frequency cannot be judged yet after 10-minute sensing, the vane motor turns to OFF. But the AIR DISCHARGE
DIRECTION display continues to be indicated.
(
2
) During cooling operation
When the cooling operation starts, the horizontal discharge is automatically set. However,
the desired discharge among four modes below-listed can be selected with the AIR DIS-
CHARGE UP/DOWN button on the remote controller.
1
100%-horizontal discharge
2
60%-downward and 40%-horizontal discharge
3
80%-downward and 20%-horizontal discharge
4
100%-downward discharge
NOTE: Discharge
2
is available only when the fan speed is HIGH.
<AUTO RETURN>
When discharge “
3
” or “
4
” continues for 1 hour with the fan speed at LOW, the discharge
direction turns to the horizontal discharge automatically.
NOTE1: After that, the discharge “
3
” or “
4
” is available by setting with the remote controller,
and it continues for 1 hour.
NOTE2: If the discharge direction changes from “
3
” or “
4
”, the direction returns to the hori-
zontal discharge when 1 hour has passed since the discharge “
3
” started.
NOTE3: If the discharge direction changes from “
3
” (or “
4
”) to the horizontal discharge, the
1-hour timer to return the horizontal discharge is canceled at that time.
(
3
) During the operation OFF, the auto vane is in the horizontal position.
(
4
) When the vane motor is out of order or the connector is badly connected, the air discharge display of the remote
controller continues.
<Remote controller display>
1
2
3
4
Changes by pushing the
AIR DISCHARGE
UP/DOWN button:
Содержание Mr.Slim PLH42AK