OC193-48
vanes do not work.
Vane motor does not work.
Limit switch does not work.
Connector is badly connected.
Vane motor is badly assembled.
Indoor controller board is damaged.
Unit stops after 5 to
20 seconds operation
Protection function has broken
Air discharge display
is OFF and air dis-
charge UP/DOWN
button is not available.
Indoor unit is regarded
as without auto vane.
Horizontal angle has
not been detected.
In this case, remote
controller is normal.
Power ON/OFF switch
is not available.
Beep sound is heard,
but display is turned to
OFF.
Beep sound is not
heard, and display
remains OFF.
Indoor/outdoor connect-
ing wire is wrong con-
nected.
Indoor/outdoor connect-
ing wire shorts.
Compressor protector
has broken.
Deicer has broken.
Remote controller has
broken.
Transmission wire is
badly connected.
Transmission wire has
broken.
Connector is badly con-
nected.
Indoor terminal block is
badly connected.
Remote controller ter-
minal block is badly
connected.
Vane motor has broken.
Vane motor relay has broken.
Limit switch has broken.
Size of cam is not proper.
Refer to check code on remote controller display.
See page OC193-46.
If drain pump has broken or coil frost protection
has worked, operation does not stop only in 5 to
20 seconds
Indoor controller has
broken.
Dip switch setting is
wrong.
Indoor controller has
broken.
Vane motor has broken.
Vane motor limit switch
is badly connected.
Auto vane is wired after
power is turned to ON.
Vane motor limit switch
has broken.
Vane motor has broken.
Badly connect
Disconnected
4. OTHER TROUBLES AND CAUSES
“Centrally controlled” is displayed.