53
Check of power supply
M
Inverter does not work.
Check of rush current limiting circuit
N
Outdoor unit does not operate.
Replace the current limiting resistor (R64).
When the current limiting resistor is open, the rush current limiting relay may not be working properly.
Therefore confirm the limiting resistor works properly after replacing it.
Does current limiting resistor (R64) detect 10
"
?
No
∞
Yes
Ok
Start
Star
Is there 208-230V AC between
terminal block L1 and L2 on
the outdoor unit?
Turn on power supply.
Check the connecting of main circuit part, and connector.
Is there 290-330V DC to
smoothing capacitor (C61)?
Replace the outdoor electronic
control P.C. board.
Check the power supply cable.
Is there 208-230V AC between
terminal TAB69 and X64 (terminal 4)?
Check the main circuit parts
and replace it.
❈
Check the
current-limiting
resistor (R64).
Is there 10
"
to current-limiting
resistor (R64)?
Replace the
outdoor electronic
control P.C. board.
Replace the
current-limiting
resistor (R64).
No
No
No
Yes
Yes
Yes
Yes
No
❈
L61 : REACTOR
DS61,62 : DIODE STACK
C61 : POWER-FACTOR CAPACITOR
C63 : SMOOTHING CAPACITOR
F801 : FUSE (2A)
OB297--2.qxp 04.2.4 4:21 PM Page 53